SmartBox
®
1 / SmartBox
®
2 / SmartBox
®
3
part no. 28 100 57 f
9 / 20
PROGRAMMING
Overfilling of the tank due to incorrect entry values.
Operating media may leak.
These:
•
are hazardous to water,
•
are category 1,2 and 3 inflammable liquids,
•
can ignite and cause burning,
•
may cause falling injuries due to slipping.
Enter these values with care!
The entry values are also retained in the event of the failure of the supply voltage.
Menu
Input function
Input value
0.Exit
Press [ENTER] to return to display mode
1.Probe
Select probe measuring range
see type label of the
probe
-
default setting
250 mbar
________mbar
Standard probe
max. tank height for
fuel oil
water
100mbar
1.20 m
1.00 m
150mbar
1.80 m
1.50 m
160mbar
1.90 m
1.60 m
200mbar
2.40 m
2.00 m
250mbar
2.90 m
2.50 m
400mbar
4.70 m
4.00 m
500mbar
6.00 m
5.00 m
1.000mbar
12.00 m
10.00 m
2.000mbar
24.00 m
20.00 m
3.000mbar
36.00 m
30.00 m
5.000mbar
60.00 m
50.00 m
Set mbar
2.Liquid
Select the
medium
_______kg/m³
Medium
Density value kg/m³ (15 °C)
Fuel oil
845 kg/m³ -
default setting
Water
999 kg/m³
Diesel
830 kg/m³
Biodiesel
880 kg/m³
RME, FAME
880 kg/m³
Rape oil
915 kg/m³
Palm oil
910 kg/m³
Motor oil
865 kg/m³
AdBlue
1090 kg/m³
Regular
petrol
743 kg/m³
Premium
petrol
750 kg/m³
Density value
Enter a special density value
with different measuring range
If the density of the stored medium is unknown, the reference height can be entered in menu
item “10.Trim height”