Limitid indikator GWG - type GWS -issue 1
10 / 12
part no. 15 382 64 c
Table 7:
Example for calculating the adjusting dimension X
Length = 1010mm
Width = 1010mm Height H = 1010mm
b = 5mm,
Rated volume of the tank = 1000L
Bushing with k = 30mm
GWG with Z = 305mm
1.
Q
max
pursuant to DIN 4755, E DWA-A 791-1, and TRbF 20
1200L/min
2. Total time
t
ges
pursuant to EN 13616
5.5s
3. Overrun volume
V
3
V
1
= 1200L/min;
(5.5s • min / 60s)
110L
V
2
for D
i
= 55mm and L
FL
= 15m
35L
V
4
= V
1
+ V
2
= 110L + 35L
145L
4. Response height
L
1
and adjusting dimension X
V
3
= 95% (
V/V
) of 1000L
950L
V
5
=
V
3
-
V
4
= 950 - 145
805L
a) Look up volume V
5
in calibration chart and find the level L
1
_ _ _ _ mm
b) Approach:
L
1
+ a - b = H -
(2 • b)
= 1000mm
1000L ≡ 1000mm
at 100% (V/V),
805L ≡
L
1
[mm]
c) from a) or b):
L
1
= 805mm
d) Adjusting dimension GWG
X = H - L
1
- b + k
= 1010 - 805 - 5 + 30
230mm
e) Control dimension GWG
Y = Z - X
= 305 - 230
75mm
LIMIT INDICATOR REPLACEMENT (OLDER TANKS)
From DIBt information issue 1/2008
When replacing limit indicators on tanks with test certificates or general approvals of the
building inspectorate, the following limit indicator with the certificate of suitability for intended
use of the building inspectorate may be installed:
•
limit indicators fitting into the designated connection on the tank,
•
limit indicators having such a length allowing for the hitherto adjusting dimension to be re-
configurable and for reading off the related control dimension.
TECHNICAL CHANGES ISSUE 1
All the information is the result of product testing and corresponds to the level of knowledge at
the time of testing and the relevant legislation and standards at the time of issue. We reserve
the right to make technical changes without prior notice. Errors and omissions excepted. All
figures are for illustration purposes only and may differ from actual designs.
DECLARATION OF PERFORMANCE
You will find the manufacturer’s
declaration of performance
for this product on
the website:
http//www.gok-online.de/en/certificate/
declaration of performance.php
•
CE marking according to EU Construction Products Directive: Declaration of
performance according to EN 13616