Check all connections from the controller to the battery including checking for 

correct wire polarity. Check that all connections are clean, tight, and secure. 

Ensure the battery voltage is above 6 volts.   

 

Display Reading:

 Nighttime 

 

 

 

Time of Day:

 Daytime 

 

Possible Causes:  

Panel is covered by something; PV panel is too dirty to supply a high enough 

voltage to charge the 

battery; PV panel is not connected.

 

 

Remedy:   

Check the panel and to ensure it is not obscured. Clean the panel if it is dirty. 

Check that PV cables are connected to the controller.  

 

 

9.2 

Problems with Voltage   

Voltage Reading:

 Inaccurate 

 

 

Time of Day:

 Daytime/Nighttime 

 

Possible Cause:  

Excessive voltage drop from batteries to controller due to loose connections, 

small wire gauge or both. 

 

How to tell:  

Check the voltage at the controller battery terminals with a voltmeter and 

compare with the voltage reading at the battery terminals.   

 

If there is a voltage discrepancy of more than 0.5 VDC, there is an excessive 

voltage drop. 

 

Remedy:  

Check all connections from the controller to the battery including checking for 

correct wire polarity. Check that all connections are clean, tight, and secure. 

Shorten the distance from the controller to battery or obtain larger gauge wire.  It 

is also possible to double up the existing gauge wire (i.e. two wire runs) to 

simulate a larger gauge wire. 

 

9.3 

Problems with Current 

Current Reading:

 0 A 

Time of Day:

 Daytime, clear sunny skies 

 

Possible Cause:  

Current is being limited below 1 Amp as per normal operation or 

poor connection between solar array and controller. 

 

How to tell: 

Summary of Contents for Dura Lite Solar Controller

Page 1: ...Solar Controller User Manual ________________________________________________________________________ 2020 Go Power User Manual 30 amp Single Bank Solar Controller...

Page 2: ...T SAFETY INSTRUCTIONS 4 3 0 Choosing a Battery 6 4 0 DuraLite Kit Wiring Diagram 6 5 0 Operating Instructions 6 5 1 Battery Charging Profile Chart 8 6 0 Errors Troubleshooting 9 7 0 Display Symbols 10...

Page 3: ...ystem voltage and is rated for a maximum continuous DC input current of 37 5A and input voltage of 35VDC Per National Electrical Code NEC article 690 7 and 690 8 PV module nameplate ratings must be mu...

Page 4: ...Current 30A Max PV Open Circuit Voltage 50V Battery Type Sealed AGM Gel Flooded Lithium 1 12V and Lithium 2 24V Self consumption 4 2mA 12V 2 6mA 24V Temperature Compensate Coefficient 3mV 2V Default C...

Page 5: ...ion Use extreme caution when working with electricity and when handling and working around batteries Observe correct polarity Reverse polarity of the Battery 1 terminals will cause the controller to g...

Page 6: ...fety instructions 4 0 DuraLite Kit Wiring Diagram The SOLAR CONTROLLER Maximum 37 5A rating is based on a 30 amp total maximum short circuit current rating Isc from the solar modules nameplate ratings...

Page 7: ...ess the SET button to clear the generated energy 3 Switch the battery temperature unit Press the SET button and hold 5s under the battery temperature interface 4 Battery type Battery type Sealed Gel F...

Page 8: ...m Sealed Gel Flooded Lithium Over Voltage Disconnect Voltage 16 0V 16 0V 16 0V 14 6 29 2V Charging Limit Voltage 15 0V 15 0V 15 0V 14 4 28 8V Over Voltage Reconnect Voltage 15 0V 15 0V 15 0V 14 4 28 8...

Page 9: ...min and boost duration is 10 to180min 2 When setting a lithium battery type for example a LiFePO4 use these rules when setting voltage parameters Over Voltage Disconnect Voltage Charging Limit Voltage...

Page 10: ...ing Solution This is an Over Discharge Error The battery voltage is too low Connect the DuraLite kit to charge the battery 7 0 Display Symbols Icon Motion Issue Solid The system is normal but not char...

Page 11: ...ed when compared with readings from another voltmeter There may be a slight difference between the battery voltage displayed on the SOLAR CONTROLLER display and the battery voltage measured at the bat...

Page 12: ...oblems is split into three sub sections grouped by symptoms involving key components A multimeter or voltmeter may be required for some procedures listed It is imperative all electrical precautions st...

Page 13: ...ssible Cause Excessive voltage drop from batteries to controller due to loose connections small wire gauge or both How to tell Check the voltage at the controller battery terminals with a voltmeter an...

Page 14: ...clean tight and secure Continue with the solutions below for additional help on low current readings Current Reading Less than expected Time of Day Daytime clear sunny skies Possible Causes 1 Current...

Page 15: ...itive and negative terminals of each module junction box with either the positive or the negative wires disconnected from the terminal Remedy 2 Reconnect in correct configuration Tighten all connectio...

Page 16: ...oper hook up Acts of God including lightning floods earthquakes fire and high winds Damage in handling including damage encountered during shipment This warranty shall be considered void if the warran...

Page 17: ...ER _______________________________________________________________________ 17 2020 Go Power 2019 GO POWER 201 710 Redbrick St Victoria British Columbia Canada V8T 5J3 MOBI_MAN_SOLAR CONTROLLER _RevF g...

Reviews: