D5062 

- SIL 2 Vibration Transducer Interface

 

G.M. International ISM0184-7 

SIL 2 Vibration Transducer Interface, 

DIN-Rail and Termination Board, 

Model D5062S 

 

D5062S 

INSTRUCTION & SAFETY MANUAL 

Summary of Contents for D5062S

Page 1: ...D5062 SIL 2 Vibration Transducer Interface G M International ISM0184 7 SIL 2 Vibration Transducer Interface DIN Rail and Termination Board Model D5062S D5062S INSTRUCTION SAFETY MANUAL...

Page 2: ...ent temperature Calibration accuracy 0 05 of full scale Linearity error 0 05 of full scale Supply voltage influence 0 005 of full scale for a min to max supply change Temperature influence 0 005 on ze...

Page 3: ...mpatibility to EN61000 6 2 EN61000 6 4 EN61326 1 EN61326 3 1 for safety system ATEX IECEx UL C UL UKR TR n 898 TIIS T V Certifications T V Functional Safety Certification Type Approval Certificate DNV...

Page 4: ...IIC E F G Co Ca 0 7 F 7 8 9 10 Ci Ci device C cable IIC A B Lo La 4 1 mH IIB C Lo La 16 4 mH IIA D Lo La 33 9 mH I Lo La 54 mH IIIC E F G Lo La 16 4 mH 7 8 9 10 Li Li device L cable IIC A B Lo Ro 56 8...

Page 5: ...P IIC SAFE AREA ZONE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D5062S 8 9 5 6 Supply 24 Vdc 7 Out 1 2 In Power 3 wires Vibrat...

Page 6: ...T4 CLASS I ZONE 2 GROUP IIC T4 Input configuration selection via internal Dip Switch 1 2 3 4 ON OFF 2 wires transducers 4 mA 1 ON 2 OFF 3 OFF 4 OFF 1 2 3 4 ON OFF 2 wires transducers 6 mA 1 ON 2 ON 3...

Page 7: ...N HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 Input configuration selection via internal Dip Switch 1 2 3 4 ON OFF 2 wires AC transducers 1 OFF 2 OFF 3...

Page 8: ...ge 20 Vdc Assuming that the application program in the safety logic solver is configured to detect High failure and does not automatically trip on this failure this failure has been classified as a da...

Page 9: ...more than 5 of full span 1 Vdc Fail High a failure mode that causes the output signal to go below the maximum negative voltage 20 Vdc Assuming that the application program in the safety logic solver...

Page 10: ...able to go to the defined fail safe state or deviates the output voltage by more than 5 of full span 1 Vdc Fail High a failure mode that causes the output signal to go below the maximum negative volta...

Page 11: ...smaller than 1 In addition impose a zero input signal and verify that the output ripple is 20 mVrms This test detects any other possible failure in the loop transfer function 4 Connect a current sinki...

Page 12: ...totally isolated circuit located in Safe Area to drive vibration monitors or analyzers for rotating machinery control and supervision purposes The module provides 3 port isolation input output supply...