PM 1001484 000 06
Device handbook SINEAX DM5000
60/87
Further settings
Alarm limit for OFF AUS:
I
OFF
= 90…75%
*)
Prewarning limit:
I
WARN
= 50%...(I
OFF
-1%)
*)
Prewarning AUS:
I
WARN
- (10…25%)
*)
Response delay:
1…10s, separately for alarm and prewarning
Dropout delay:
1…300s, separately for alarm and prewarning
*)
All percent values are related to the alarm limit (100%)
Interfaces
Ethernet
via RJ45 socket
Protocol:
Modbus/TCP, NTP, http
Physics:
Ethernet 100BaseTX
Mode:
10/100 Mbit/s, full/half duplex, auto-negotiation
IEC61850
via RJ45 sockets, 2 equivalent ports
Protocol:
IEC61850, NTP
Physics:
Ethernet 100BaseTX
Mode:
10/100 Mbit/s, full/half duplex, auto-negotiation
Modbus/RTU
via plug-in terminal (A, B, C/X)
Protocol:
Modbus/RTU
Physics:
RS-485, max. 1200m (4000 ft)
Baud rate:
9'600, 19'200, 38'400, 57'600, 115'200 Baud
Number of participants:
≤ 32
Internal clock (RTC)
Uncertainty:
± 2 minutes / month (15 up to 30°C)
Synchronization:
none, via Ethernet (
) or
Running reserve:
> 10 years
Uninterruptible power supply (UPS)
Type:
VARTA Easy Pack EZPAckL, UL listed MH16707
Nominal voltage:
3.7V
Capacity:
1150 mAh min., 4.5 Wh
Operating duration:
5 times 3 minutes
Life time:
3 up to 5 years, depending on operating and ambient conditions
Ambient conditions, general information
Operating temperature:
• Device without UPS: –10 up to 15 up to 30 up to + 55°C
• Device with UPS: 0 up to 15 up to 30 up to + 35°C
Storage temperature:
Base device: –25 up to + 70°C;
Battery pack UPS: -20…60°C (<1 month); -20°…45°C (< 3 months);
-20…30°C (< 1 year)
Temperature influence:
0.5 x measurement uncertainty per 10 K
Long term drift:
0.5 x measurement uncertainty per year
Others:
Usage group II (EN 60 688)
Relative humidity:
< 95% no condensation
Altitude:
≤ 2000 m max.
Device to be used indoor only!