Global Fire Equipment Vulcan 2 DS Quick Start Manual Download Page 1

TECHNICAL SPECIFICATIONS

Vulcan 2 DS

Detector Sounder/ Beacon

ORDER CODE

DESCRIPTION

VULCAN 2 DETECTOR SOUNDER

VULCAN 2 

 SOUNDER WITH ISOLATOR

VULCAN 2 DETECTOR SOUNDER WITH BEACON

VULCAN 2 DETECTOR SOUNDER WITH BEACON WITH ISOLATOR

VULCAN 2 DETECTOR BEACON

VULCAN 2 DETECTOR BEACON WITH ISOLATOR

LID FOR VULCAN 2

TRANSPARENT LID FOR VULCAN 2

DETECTOR

VULCAN 2 DS
VULCAN 2 DSI
VULCAN 2 DSB
VULCAN 2 DSBI
VULCAN 2 DB
VULCAN 2 DBI
VULCAN 2 L
VULCAN 2 LT

NOTE: 

Add to sounder/ beacon current when active, conventional detector current in alarm which is internally limited to a maximum of 12 mA. 

Loop In/Out

Address|A|B|S

- V
ol +

Tone

T

- Mode

M

Loop In/Out

Detector
Sounder

LOOP

OUT

LOOP

RETURN

PANEL

Detector

Base

Volume

Adjustment

red wire

black wire

Normal Sounder

Optical Detector

T M

1 2 3 4

Heat Detector

T M

1 2 3 4

Mode Selection

- Tone

- Mode

T M

ALTERNATING

LOW-FREQUENCY TONE

800-1000 Hz

T M

T M

T M

T M

SWEEPING

TONE

800-1000 Hz

ALTERNATING

HIGH-FREQUENCY TONE

2.7 KHz-3.2 KHz

CONTINUOUS

TONE

800 Hz

CONNECTIONS AND TONE/MODE SETTINGS

When connecting the conventional detector always follow the manufacturer’s instructions to ensure proper operation.

NOTE:

 If Mode (M) SW 3 & SW 4 are set to OFF, the device will behave like a 

normal addressable sounder

.

In this mode no detectors, conventional or analogue addressable can be connected to this sounder unit.

The 

shadow sounder mode

 will still be available by placing switch no. 8 in the OFF position.

SOUNDER

2.5 mA
5 mA
2.5 mA
2.5 mA

SOUNDER/BEACON

3.3 mA
6.4 mA
3.3 mA
3.3 mA

SOUNDER W. ISO.

2.65 mA
5.15 mA
2.65 mA
2.65 mA

SOUNDER/BEACON W. ISO.

3.45 mA
6.55 mA
3.45 mA
3.45 mA

SUPPLY VOLTAGE
LOOP CURRENT - QUIESCENT
LOOP CURRENT - SOUNDER/BEACON ACTIVE
Sweeping Tone 800-1000 Hz
Alternating High Freq. 2.7-3.2 KHz
Continuous Tone 800 Hz
Alternating Low-Freq. 800-1000 Hz
LOOP CURRENT - BEACON
MAXIMUM SOUNDER OUTPUT
CABLE SIZE
RESET/START-UP TIMES
PROTECTION CATEGORY
COLOUR / CASE MATERIAL
OPER. TEMPERATURE / MAX. HUMIDITY
DIMENSIONS / WEIGHT

Loop Powered - 20V to 30V DC
430 uA & 550 uA with isolator - add conventional detector quiescent current

Beacon 2.5 mA Beacon with isolator 2.7 mA
97 dB (@ 1 meter - 30 V DC)
0.5-2.5 mm²
20 seconds max.
Type A - Indoor Use - Rating IP21C
White or Red / ABS

o

o

-10 C to 55 C / 95% RH Non-Condensing
100 (D) x 50 (H) mm inc. base / 144 g inc. base

MADE IN PORTUGAL - EU

ma_vulcan2ds_01_010002_en_220103