POWER SUPPLY SPECIFICATION – MEANWELL MODEL: EPS-65-28.EOL
MAINS SUPPLY VOLTAGE
90-264 V 50/60 Hz
INTERNAL POWER SUPPLY
Min. 20V DC - Max. 30V DC
(28.5 V DC nominal) Max. Ripple 1 V peak-peak
TOTAL OUTPUT CURRENT
2,27 Amp @ 230V AC
SUPPLY AND BATTERY CHARGER MONITORED
YES
BATTERIES MONITORED
YES
MAX BATTERY SIZE
2 x 12 V 12AH VRLA
MAINS FUSE
4 A - 250 V Slow Blow - 20 mm
Voltage
Primary supply voltage
90 - 264V AC
EMC Standard
EN55022 class B
EN61000-4-2,3,4,5,6,8,11
EN61000-3-2,3
Current
2.4 A PSU’s recommended for 1 to 4 loop panels.
The maximum alarm sounder current is 250 mA for each conventional sounder circuit.
The maximum quiescent current per loop is 165 mA. The loop short circuit (trip) current is 900 mA.
Battery
Internal maximum capacity 24 V / 12 AH.
Please use a minimum of 7 Ah Battery Capacity.
BATTERY REQUIREMENTS
The battery Ampere per hour “Ah” required are calculated from the following formula:
(
Quiescent current in mA
of the panel with
everything connected
X
Standby time
required in hours
divided by 1000
)
+
(
Alarm current in Amps
(sounder load)
X
Alarm time
in hours
)
+
20%
Round up to the next available battery size. Quiescent currents for individual equipments are listed below:
EQUIPMENT
QUIESCENT CURRENT (mA)
ALARME CURRENT (mA)
OCTO+ (4 LOOPS)
73
127
NODE+ (4 LOOPS)
51
101
(
Quiescent current in mA
of the panel with
everything connected
X
Standby time
required in hours
divided by 1000
) + (
Alarm current
in Amps
(sounder load)
X
Alarm time
in hours
) + 20%
NODE+ / Installation & Commission Manual / © GFE 220331