background image

GFE-DHA

Addressable Magnetic Door Holder

Instruction Manual V1.0- 06/10

1

The  unit  is  a  loop  powered  addressable 
magnetic  door  release.  It  does  not  require 
external supply as it is directly powered from 
the loop.

Activation of the unit is achieved using cause 
and effect programming as used for I/O units.

If power is removed or communication with 
the  panel  is  lost  the  unit  will  release 
automatically  after  approximately  20 
seconds.

A  built  in  loop  isolator  is  provided. When  a 
short  condition  exists  in  either  side  of  the 
loop  connections,  a  YELLOW  LED  will  be 
turned  ON.  Its  operation  will  be  reset  after 
the fault condition is removed.

Module is fitted with 3 status leds. The GREEN 
LED will flash every time the device is polled   
by the addressable panel.

The  RED  LED,  when  ON,  indicates  that  the 
door release has been activated and it is OFF 
after panel power up or reset. When flashing, 
it indicates that the door holder is ready to 
release. Finally the YELLOW LED will indicate a 
fault in the module.

The activation of the module can be achieved 
as part of the cause and effect programming 
of the panel and it operates in the same way 
as an I/O unit. This unit should normally be 
added to an IO group and assigned to either a 
specific device or zone.
 
Up to a maximum of 20 of these units can be 
fitted on a particular loop.

Built-in Loop Isolator

Addressable Unit

Loop Powered

Loop Powered

4 Status Indicators:
Coms, Fault, Released, Isolator

Max. 20 units per Loop

Weight (Magnet)

Weight (Keeper)

Weight - complete unit boxed

Dimensions (Magnet)

Dimensions (Keeper)

Max. Humidity

Operating Temperature

Magnet Holding Force

Loop Current - Charging

Isolator - Loop Line Resistance

Charge up time

Fail Safe Release Time 

1)

Manual Release

Max. Cable Size

Loop Current - Quiescent

Technical Specifications

Supply Voltage
Address Range

7 mA

60 mOhms

25 s
20 s

Push Button - Normally Open

2

2.5 mm

520 g - boxed inc. electronic module

139 g
700 g

112.5 (H) x 84.2 (W) x46.8 (D) mm

55 (H) x 55 (W) x 50 (D) mm

º

C to 40 

º

C

200 N 

95% RH Non-Condensing

Loop Powered - 17V to 30 V DC

1-125

600 uA (450 uA 150 uA isolator)

1) Fail Safe Release Time is defined as the time taken to release door when removal 
of loop power or loss of communication with control panel is detected.

112.5 mm

46.8 mm

112.5 mm

Mechanical Specification

Global Fire Equipment S. A.

MARF - Armazéns F3 e F4, Sítio do Guelhim, Estói, 8009-021 FARO, PORTUGAL

Tel: + 351 289 896 560 Fax: + 351 289 865 587

Sales

  [email protected]  

Technical Support

 [email protected]

GFE-DHA

Order Code

Addressable Magnetic Door Holder

Reviews: