Glamox MIX LED
User manual
Page 1: ...Glamox MIX LED User manual ...
Page 2: ... av slikt avfall Eesti Meie toodete kohta kohaldatakse 2012 19 EU WEEE elektri ja elektroonikaseadmetest tekkinud jäätmete direktiivi ning nad peavad olema eluea lõppedes eraldi kokku kogutud ning toimetatud piirkonna jäätmete vastuvõtupunkti Nederlands Onze producten zijn onderworpen aan de Richtlijn 2012 19 EU Waste Electrical and Electronic Equipment WEEE en moeten aan het einde van hun levensd...
Page 3: ...luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person Live parts inside RISK OF ELECTRIC SHOCK Norsk Lyskilden i denne armaturen skal kun byttes av Glamox Glamox sin serviceansvarlig eller en tilsvarende kvalifisert person Strømførende deler på innsiden FARE FOR ELEKTRISK STØT Svenska Ljuskällan i denna armatur får endast bytas ut i Glamox fabriker...
Page 4: ...e Non emergency 220 240V AC 50 60Hz and DC Emergency 110 240V AC 50 60 Hz Supplied current mains mode 0 1 0 26A Power factor 0 90 0 95 Light modules LED For more information please see www glamox com Types L1 C1 L C Hood nuts M8 distance IP code MIX 600 LED 724 704 681 400 430 500 IP 66 67 MIX 1200 LED 1334 1314 1291 700 950 500 IP 66 67 MIX 1500 LED 1634 1614 1591 700 1100 IP 65 67 MIX LED X Spec...
Page 5: ...x 112 20556 Torque value for screws 1 8Nm Type and size of wires that can be used Solid wire From 1 0mm to 6 0mm Stranded wire with or without ferrule From 0 75mm to 6 0mm There can only be connected one wire on each side of the screw on each side of each terminal totally max 4 wires at each terminal Earthing the luminaire The luminaire must be earthed in the terminal block It can also be earthed ...
Page 6: ...E HF E HF 3 N 1 2 L N L4 N4 L N L4 N4 6 Installation and operation HF E Emergency luminaire HF No emergency DALI version comes for no emergency and emergency For HF E unswitched power supply to L4 N is needed Mains shall be from same sircuit breaker Wiring with 1 poled switch for main light N L4 unswitched Wiring without switch for main light Loop L L4 for HF E ...
Page 7: ... 1 5h 27 MIX 1200 LED 5000lm 3 0h 13 MIX 1500 LED 7500lm 1 5h 19 MIX 1500 LED 7500lm 3 0h 9 LED indicator Green Red codes is like this Normal mode battery charging Constant Green Battery failure voltage capasity Flashing Red LED module failure short circuit open loop Constant Red Test ongoing Flashing Green Emergency Mode deaktivated Flashing Green Red To have a fully charged battery charging time...
Page 8: ...85 mm 9 8 MIX LED mounting 1 2 3 4 With plastic folio at diffuser Remove plastic folio before powering 5 8 6 7 10 ...
Page 9: ...nction control to be carried out regularly Full emergency duration test by switching off power supply should be performed at least once a year Cycling of batteries at least 2 times yearly is recommended This will increase the lifetime of batteries Use only original spare parts from Glamox 1 2 Nm 11 12 13 ...
Page 10: ...10 ...
Page 11: ... The connection of L4 N the battery and the charging unit Check if battery is connected and OK The Emergency module or battery might be defect Emergency illuminance level is too low Clean the cover of the luminaire Change the battery Emergency lighting time is under the specified time 1 5 or 3 0 hours for standard luminaire Change the battery Manufacturer Glamox AS Birger Hatlebakks veg 15 NO 6405...
Page 12: ...Please visit our web site for contact information www glamox com Please refer to our website for information about our 5 year warranty Glamox March 2020 Item no 72597055 ...