Gira KNX 213900 Operating Instructions Manual Download Page 1

Operating instructions

82406412 / 29.08.2022

Heating actuator 6-gang with controller

Order no. 2139 00

Summary of Contents for KNX 213900

Page 1: ...Operating instructions 82406412 29 08 2022 Heating actuator 6 gang with controller Order no 2139 00...

Page 2: ...onents 4 3 Function 5 4 Operation 7 5 As delivered state 10 6 Information for electrically skilled persons 11 6 1 Mounting and electrical connection 11 6 2 Commissioning 13 6 2 1 Safe state mode and m...

Page 3: ...ectric shock Always disconnect before carrying out work on the device or load Danger of electric shock Device is not suitable for disconnection from supply voltage The load is not electrically isolate...

Page 4: ...s A1 to A6 3 Status LEDs for outputs 4 Button field for manual operation 5 Programming button and LED 6 Bus connection If all of the status LEDs 3 are flashing 2 Hz the device is indicating that there...

Page 5: ...issioning of the device are carried out with the aid of the ETS version 5 7 7 and above Intended use Switching of electrothermal valve drives for heaters or cooling ceilings Operation in KNX system In...

Page 6: ...ffected output group A1 A3 or A4 A6 first Unambiguous monitoring determines the overloaded output in up to 4 test cycles If in the event of only a minor overload it is not possible to unambiguously id...

Page 7: ...ves open and close according to their characteristics Valve drive Status LED on Status LED off Deenergised closed Heating cooling Valve opened Valve closed Deenergised opened Valve closed Heating cool...

Page 8: ...s the button for at least 5 seconds LED is illuminated status LED A1 flashes permanent manual operation mode is switched on Switching off permanent manual operation mode The device is in permanent man...

Page 9: ...nt manual operation mode Press the button briefly as many times as necessary until the desired out put is selected The status LED of the selected output flashes Press buttons Open and Close simultaneo...

Page 10: ...e KNX In the as delivered state all the valve outputs are configured as follows Valve direction of action Deenergised closed Pulse width modulation on Open valve 50 Cycle time 20 minutes Behaviour in...

Page 11: ...DIN rail Connecting the device Connect either AC 230 V or AC 24 V valve drives to all the outputs Only connect valve drives with the same characteristics to each output deenergised closed opened Do no...

Page 12: ...nection of 24 V valve drives Connect the supply for the valve drives to the terminals 8 L and 8 N 1 Connect bus line with device connection terminal observing the correct polar ity Attach the cover ca...

Page 13: ...sing the programming button again the programming mode can also be switched on and off in the safe state mode as usual If the program ming mode is active the programming LED stops flashing Deactivatin...

Page 14: ...a ETS Service App This func tion uses the firmware contained in the device that was active at the time of delivery as delivered state Restoring the factory settings causes the device to lose its phys...

Page 15: ...on current max 0 3 A 2 min Number of drives per output 230 V drives max 4 24 V drives max 2 Housing Installation width 72 mm 4 HP Connection of outputs Connection mode Screw terminal Single stranded...

Page 16: ...pletely for approx 5 seconds switch off miniature circuit breaker Then switch on again In case of overload initially one or both output groups switch off for approx 6 minutes After that the device det...

Page 17: ...specialist trade installation company elec trical specialist trade They will forward the devices to the Gira Service Center Gira Giersiepen GmbH Co KG Elektro Installations Systeme Industriegebiet Me...