"DALI Gateway C00CX2 EN / C00CX4 EN" software
Object table
Best. Nr. 1060 00
Page 25 of 136
Function: DALI
monitoring
Object Function
Name
Type
DP
type Flag
211
Message
DALI voltage failure
1-bit
1.005
C, -, T, (R)
Description:
1-bit object for reporting a mains voltage failure at the DALI Gateway.
(mains voltage available = 0, mains voltage failure = 1)
Function: DALI
monitoring
Object Function
Name
Type
DP
type Flag
212
Message
DALI short-circuit
1-bit
1.005
C, -, T, R
1
Description:
1-bit object for reporting a short-circuit in the DALI line.
(no short-circuit = 0, short-circuit = 1)
Function: Central
function
Object Function
Name
Type
DP
type Flag
213
Switching
Central function
1-bit
1.001
C, W, – (R)
1
Description:
1-bit object for the central switching of assigned DALI groups. The polarity can be
parameterized.
Function: Manual
control
Object Function
Name
Type
DP
type Flag
214
Disable
Manual control
1-bit
1.003
C, W, – (R)
1
Description:
1-bit object for disabling the keys for manual control on the device. The polarity can be
parameterized.
Function: Manual
control
Object Function
Name
Type
DP
type Flag
215
Status
Manual control
1-bit
1.002
C, -, T, (R)
1
Description:
1-bit object for the status transmission of manual control. The object is "0", when
manual control is deactivated (bus mode). The object is "1", when manual control is
activated. The user can determine whether the temporary or the permanent manual
control will be displayed as status information.
1
Each communication object can be read-out. The readout requires the setting of the R flag.