"DALI Gateway C00CX2 EN / C00CX4 EN" software
Functional description
Best. Nr. 1060 00
Page 90 of 136
In case a connection link to the DALI Gateway can not be established in this situation, the plug-in will
abort the commissioning prematurely and will not show the commissioning environment. The following
lists the possible causes for a faulty connection and their corresponding remedies...
–
Cause: no functioning ETS 3 communication interface to the KNX/EIB.
Remedy: verify the connection in the ETS 3 under “Tools
– Options – Communication" .
If needed,
set up the connection.
–
Cause: the physical address and the application program have not been programmed via the ETS 3.
Remedy: close the plug-in and program the physical address and the application program first.
–
Cause: KNX/EIB bus voltage at the DALI Gateway or at the local data interface is not connected or
switched on.
Remedy: connect and switch on bus voltage.
–
Cause: mains voltage supply on the DALI Gateway is not switched on.
Remedy: switch on the mains voltage supply on the Gateway.
Figure 35: Establishing a bus connection to the DALI Gateway for the DALI commissioning
Once completed the DALI commissioning can proceed, for example, by assigning the DALI devices to
the groups.