"DALI Gateway C00CX2 EN / C00CX4 EN" software
Functional description
Best. Nr. 1060 00
Page 59 of 136
Set the "Response to bus voltage return" parameter in the "Groups - [x] group name" parameter
node to the required behaviour.
After bus or mains voltage return, the parameterized state will be adopted in the "Forced-control
position" communication object. In case of an active forced-control position, the group will be
addressed and locked by forced control immediately after the return of bus/ mains voltage to the
corresponding state until the forced-position condition is cancelled via the bus. In this case the
"Response to bus voltage return" parameter in the "Groups - [x] group name" parameter node will not
be evaluated for the affected group.
When set to “Status as prior to bus voltage failure” the status of the forced-control position that was
last set and stored internally prior to bus or mains voltage failure will be resumed after the return of
bus or mains voltage. An ETS programming operation will delete the stored state (reaction same as
“No forced-control position active”).
If the tracked “No forced-control position” state is active, the “Response to bus voltage return”
parameter, which is independent of forced control, will be executed after the bus voltage returns. In
case of an activated forced-control position the DALI devices of the group will be switched on to the
brightness value provided by the “Brightness for forced-control position active, ON” parameter.
After programming the application or the parameters with the ETS, the forced control position
function will always be deactivated (object value "0").