Deactivating the temporary manual control mode
Temporary manual control mode has been activated.
No key-press for 5 s
- or -
select all groups successively by a brief press of the key. Now press the key once more.
- or -
Shut off power supply or reset bus (bus voltage return).
The temporary manual control mode is now terminated. The 7-segment display will extinguish.
When shutting off the temporary manual control mode, the state selected by manual control will not
change. If, however, a forced-control position or a disable function has been activated via the bus
prior or during the manual control, the DALI Gateway will execute the disable or forced responses for
the affected groups.
Activating the permanent manual control mode
The DALI Gateway has been programmed at least once via the ETS.
Manual control has been enabled in the ETS. Bus mode or temporary manual control mode has been
activated.
Press the key for at least 5 s
The status LED lights up. The group number “01” will be shown on the 7-segment display.
Permanent manual control mode is now activated:
Deactivating permanent manual control mode
Permanent manual control mode is activated.
Press the key for at least 5 s
- or -
Shut off power supply or reset bus (bus voltage return).
The permanent manual control mode for broadcast has now been terminated. The status LED and
the 7-segment display will extinguish.
Depending on how the Gateway has been parameterized in the ETS, the groups will be set to the
state last adjusted via manual control or to the state internally tracked (direct control, forced-control
position / disable function) when shutting off the permanent manual control.