"DALI Gateway C00CX2 EN / C00CX4 EN" software
Parameters
Best. Nr. 1060 00
Page 133 of 136
Staircase timer function (applies only to DALI groups 1...16!)
Staircase timer function
?
Yes
No
This parameter can enable the Staircase
timer function and the corresponding
communication objects.
Staircase lighting time
00:00:01 … 23:59:59
[hh:mm:ss]
2 min
This parameter is used for programming
the duration of the Staircase timer function.
This parameter will be visible only if the
Staircase timer function has been
enabled.
Staircase lighting time
retriggerable ?
Yes
No
An active switch-on time can be retriggered
(setting "Yes"). Alternatively, retriggering
can be suppressed (setting "No").
This parameter will be visible only if the
Staircase timer function has been
enabled.
Response to OFF
telegram
Switch-off
Ignore
An active switch-on time can be cancelled
prematurely by switching off the Staircase
timer function.
The staircase lighting time is cancelled if an
OFF-telegram to the "Staircase timer start /
stop" object has been received.
OFF telegrams will be ignored. The switch-
on time will be fully completed.
This parameter will be visible only if the
Staircase timer function has been
enabled.
Activate pre-warning
time ?
Yes
No
Once the switch-on time of a Staircase
timer function has ended, the DALI devices
of the group are able to produce a pre-
warning prior to the shutoff (brightness
reduction). The pre-warning function is
designed to warn anyone present in the
staircase that the lights will go out shortly.
The pre-warning function is activated.
The pre-warning function is deactivated.
This parameter will be visible only if the
Staircase timer function has been
enabled.