Fitting, electrical connection and operation
Best. Nr. 1060 00
Page 13 of 136
Priorities
The DALI Gateway distinguishes between different functions that can affect a DALI group. In order to
prevent conflicting output states, each available function has been assigned a certain priority. The
function with the higher priority overrides the one with the lower priority.
–
1
st
Priority: Manual control mode (highest priority)
–
2
nd
Priority: Forced-control position or disable function
–
3
rd
Priority: Direct bus mode (“Switching” & “Dimming” & “Brightness value” objects, scenes, centra
function)
Switching on the temporary manual control for the broadcast function
The manual control for the broadcast function can be utilized while the DALI Gateway is in the
unprogrammed state. As in this case no group configurations have been stored due to a missing ETS
programming, the DALI Gateway will collectively control the connected DALI devices in manual control
per broadcast command.
The DALI Gateway has not yet been programmed via the ETS.
Press the key briefly (< 1 s).
"
" is shown on the 7-segment display.
After 5 s without key-press, the Gateway will deactivate the manual control for the broadcast.
The Gateway is delivered with the broadcast mode activated. After programming via the ETS, it is
also possible to reactivate the broadcast mode any time by unloading the application program via the
ETS.
Switching on the temporary manual control for broadcast
The DALI Gateway has not yet been programmed via the ETS.
Temporary manual control mode for the broadcast has been activated.
No key-press for 5 s
- or -
Press key twice.
- or -
Switch off mains voltage supply.
Temporary manual control mode for broadcast has now been terminated. The 7-segment display will
extinguish.
When shutting off the temporary manual control mode for broadcast, the state selected by manual
control will not change.
Switching on permanent manual control mode for broadcast
The DALI Gateway has not yet been programmed via the ETS.
Manual control mode or temporary manual control mode for broadcast has not been activated.
Press the key for at least 5 s.
The status LED is illuminated. "
" is shown on the 7-segment display. Permanent manual
control mode for broadcast has been activated