"DALI Gateway C00CX2 EN / C00CX4 EN" software
Parameters
Best. Nr. 1060 00
Page 124 of 136
Response to bus voltage
return
No forced-control position
active
Status as prior to bus voltage
failure
Forced-control position active,
switching off
Forced-control position active,
switching on
The communication object of the forced-
control position function can be initialized
after bus voltage return. The brightness
status of the DALI group can be influenced
if the forced-control position function is
activated.
No forced-control position will be activated
after bus voltage return.
The status of the forced- control position
will be set to the status that was
permanently stored at the time of bus
voltage failure. After programming the
application or the parameters with the ETS,
the value is internally set to "not active". In
case of an activated function the DALI
devices of the group will be switched on to
the brightness value provided by the
“Brightness for forced-control position
active, ON” parameter.
The forced-control position will be
activated. The DALI devices of the group
will be switched off by forced control.
The forced-control position will be
activated. The DALI devices of the group
will be switched on to the brightness value
provided by the “Brightness for forced-
control position active, ON” parameter.
After programming the application or the
parameters with the ETS, the forced-
control position will always be deleted.
This parameter becomes visible only if
the forced-control position function has
been enabled.