2.4 Commissioning
After installation of the Gateway and connection of the bus line and the mains supply as well as the
DALI lines, the device can be put into operation. The following procedure is generally recommended...
DANGER!
Electric shock in case of accidental contact with live parts. Electric shocks can be fatal.
Before working on the device, cut out the mains supply and cover up live parts in the
surroundings.
Commissioning the device
Switch on the mains supply of the Gateway.
Switch on the bus voltage
Checking the voltages: the red programming LED must light up when the programming key is being
pressed.
Program and project the physical address with the ETS.
The DALI Gateway is configured via a plug-in which is integrated into the ETS database. Start the
plug-in (open the parameter view) and configure the KNX/EIB groups (cf. Chapter 4 “Software
description”). Do not yet commission the DALI!
Close the plug-in and download the application program with the ETS.
Restart the plug-in (open the parameter view) and commission the DALI (cf. Chapter 4 “Software
description”).
Close the plug-in in order to save the DALI configuration in the ETS database. Then proceed with
downloading the application program again.
The DALI Gateway is now ready for operation.
ETS programming will not be possible if the mains voltage is not connected to the DALI Gateway.
The ETS plug-in will display a message during the closing, if the application program of the DALI
Gateway has to be reprogrammed in the cases described.