Gira 2105 02 Operating Instructions Manual Download Page 9

Range 

Ø approx. 20 m (installation height 3 m) 

Brightness sensor 
Measuring range 

0 ... 2000 lx 

Detection area 

Ø 2 m 

6.2 Troubleshooting 

Light does not switch on despite motion detection and low lighting 

Cause 1: Wrong function block active. 

Change function block switch-over. 

Cause 2: Brightness threshold set is too low. 

Increase the brightness threshold with the remote control or parameter setting. 

Light switches on despite sufficient ambient lighting 

Cause 1: Signal function is active and the device therefore operates independently of the 
brightness. 

Check programming. 

Cause 2: Device operates independently of the brightness. 

Adjust the brightness threshold with the remote control. 
Adjust parameter setting for brightness threshold. 

Light switches off briefly and then on again immediately 

Cause 1: Light bulbs in the detection area. 

Set the configuration barrier parameter so that cooling light bulbs are not detected. 

Cause 2: The brightness threshold set is not reached after switching off. Device switches on 
again immediately during motion detection. 

Increase brightness threshold. 

Light switches off early despite motion detection and low lighting 

Cause 1: The set time is too short. 

Increase the time with the remote control or parameter setting. 

Cause 2: Detection problem, the surface to be monitored is not in the detection area, or 
furniture or pillars are in the way. 

Check detection field, extend presence detector extension if necessary. 

Device responds even without any motion in the detection field 

Cause: Interference sources in the detection area or device are set too sensitively. 

Limit detection area, remove interference sources. 
Adjust sensitivity by one level with adjuster 

Sens. 

(6) or with remote control. 

Reduce sensitivity in parameter setting. 

The sensitivity should be reduced by 1 to 2 levels in small spaces. 

Light does not switch off despite sufficient ambient lighting 

Cause 1: Device is set as motion detector and therefore does not evaluate the ambient lighting 
after reacting. 

Check programming. Set and program device as presence detector. 

Cause 2: Brightness threshold set is too high. 

Decrease the brightness threshold with the remote control or parameter setting. 

Light does not switch on or switches on too late despite motion in the detection field 

Cause 1: Device is set for alert operation and does not evaluate the first motion impulse 
detected. 

Check programming. Set and program device as motion detector.  

82585602 

20.09.2012 

9/10 

KNX/EIB 

Presence detector 

Summary of Contents for 2105 02

Page 1: ...ow Device can be damaged The device is not suitable for use as a burglar alarm or other alarm Caution Damage to sensors may result due to high thermal radiation Avoid direct sunlight penetration in th...

Page 2: ...tment of sensitivity Status LED Flashes during motion detection depending on programming in normal operation or only during the walking test mode Additional characteristics of Comfort version Manual o...

Page 3: ...Function block 1 Brightness independent operation Function block 1 Set current brightness as brightness threshold Function block 1 Extend minimum run on time 10 seconds by the selected value Function...

Page 4: ...seconds can be extended individually o Extend run on time Depending on requirement press button button button button or button Other values can be set with the buttons 5 Information for electrically s...

Page 5: ...is installed on the ceiling and monitors the surface below it When used as a motion detector the device is installed e g in the hallway on the ceiling o Select a vibration free installation location V...

Page 6: ...ea I cut out approx 7 5 m Areas I II cut out approx 12 m without push on cover approx 20 m o Pull off push on cover o Using scissors cut out push on cover along the marked lines as required o Push on...

Page 7: ...n a flush mounted box Flush mounted appliance box is mounted on the ceiling at the designated installation location o Pull off decor ring 3 o When mounting the supporting frame 1 make sure that the ar...

Page 8: ...connected The physical address and application software are loaded o Activate walking test Activate parameter walking test after download and download application software The presence detector opera...

Page 9: ...hting Cause 1 The set time is too short Increase the time with the remote control or parameter setting Cause 2 Detection problem the surface to be monitored is not in the detection area or furniture o...

Page 10: ...r No 2116 00 6 4 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade Please submit or send faulty devices postage paid together with an error descripti...

Reviews: