7. Oil pump
The pump pressure can be set for the respective output (see Adjustment table, page 14).
For this:
• unscrew sealing plug
➃
• screw in the manometer and set the pump pressure via the adjusting screw
➅
.
The pump pressures specified in the adjustment table are only reference values and can, if necessary, be
deviated from i.a.w. the system conditions.
Caution:
The full pump pressure at the manometer is only available to the "Suntec AS47" oil pump after the
oil supply release!
Suntec:
➀
= Feed
➁
= Return
➂
= Pressure pipe connection
➃
= Pressure gauge connection
➄
= Vacuum gauge connection
➅
= Pressure setting
➇
= Solenoid valve
Danfoss:
• unscrew pressure gauge connection
➃
• screw in manometer and set pump pressure with pressure
setting
➅
i.a.w. the adjustment table.
➀
= Feed
➁
= Return
➂
= Pressure pipe connection
➃
= Pressure gauge connection
➄
= Vacuum gauge connection
➅
= Pressure setting
➇
= Solenoid valve