26. Troubleshooting
Defect determined:
Flash code DMG
972
Cause:
Remedy:
Burner motor does not
start up
-
Electric supply lead faulty
Rectify faults in electrical installation
-
Fuse faulty
Replace
-
Safety thermostat locked out
Unlock
-
Temperature of controller set-
ting is exceeded
Renewed start attempt after tempera-
ture drop
-
Control box faulty
Replace
-
Leak
Rectify leak
-
No gas
Safeguard gas supply
-
Gas pressure monitor faulty
Replace gas train
-
Filter in gas train dirty
Clean or replace
Burner motor faulty
Replace
-
No load at terminal 5
Check plug connection and current
path of solenoid valve
Mains voltage < 187 V
Rectify faults in electrical
installation
Burner starts up and
switches to fault mode
before or after expiry of
safety period
Ionisation signal
Solenoid valve leaking
Air pressure switch does not
switch through during pre-venti-
lation
See Page 21
Ionisation monitoring device
affects ignition
See Page 21
Gas solenoid valve does not
open
Replace gas train
Starting gas flow set too low
Increase starting gas flow
No ignition
Check ignition electrode and setting,
ignition transformer and cable
(see Page 11)
Phase and zero mixed up
Connect connector unit in correct
phase sequence
Ionisation monitoring device
faulty
Check according to Page 21
Air pressure switch switches
during operation
See Page 21
Gas nozzle dirty or faulty
Replace gas nozzle
Flame extinguishes
during operation
-
No gas
Safeguard gas supply
-
Filter in gas train dirty
Clean or replace
Flame blow-off
Wrong burner setting
(see Pages 13-14)
Air pressure switch contact
opens
Check/replace air pressure switch
(see Page 21)
Flame signal too weak
Measure the flame signal, check the
ionisation electrode
(see Page 21)
Burner motor starts up
briefly. Control unit
switches to fault mode
Any failure flash code
Control unit was not reset
Reset control unit fault
Air pressure switch not in idle
position
Check air pressure controller
Control box resets auto-
matically
Intermittent fault
(10 sec.)
Gas pressure monitor
cause brief (1-5 sec.) gas pres-
sure fluctuations
Ensure that the gas supply is intact
and set the gas pressure switch and
*a lower start point if necessary
Service instructions/dimensions