OWNER’S & INSTALLATION 

 MANUAL 

WIRED CONTROLLER

Thanks for choossing our product. 

Please, read carefully this manual 

before using the product 

ENGLSI

H

Summary of Contents for GIATSU GIA-XK46

Page 1: ...GIA XK46 OWNER S INSTALLATION MANUAL WIRED CONTROLLER Thanks for choossing our product Please read carefully this manual before using the product ENGLSIH...

Page 2: ...ect to actual operation 3 In order to make the product better we will continuously conduct improvement and innovation We have the right to make necessary revision to the product from time to time due...

Page 3: ...1 ON OFF 28 6 2 MODE SETTING 28 6 3 TEMPERATURE SETTING 29 6 4 FAN SETTING 30 6 5 TIMER SETTING 31 6 6 SWING SETTING 38 6 7 QUIET SETTING 39 6 8 SLEEP SETTING 42 6 9 AIR SETTING 43 6 10 LIGHT ON OFF S...

Page 4: ...n may cause severe damage or death to people This sign indicates that the items must be observed Improper operation may cause damage to people or property WARNING This product can t be installed at co...

Page 5: ...ng on that of master indoor unit Master indoor unit can switch to any modes while slave unit can t switch to the mode that is conflicting with master indoor unit When master indoor unit changes mode w...

Page 6: ...Wired controller GIA XK46 6 Wired Controller XK46 3 3 DISPLAY Fig 3 1 Appearance of wired controller 3 1 LCD OF WIRED CONTROLLER Fig 3 2 LCD graphics of wired controller...

Page 7: ...then the temperature zone will display FAP 6 Cooling mode 7 Dry mode 8 Fan mode Heating mode Wired Controller XK46 5 9 Instructions 10 When inquiring or setting project number of indoor unit it displ...

Page 8: ...ave status of indoor unit 32 It indicates the current wired controller is the slave wired controller address of wired controller is 02 33 Memory status The indoor unit resumes the original setting sta...

Page 9: ...Switch among auto low speed low medium speed medium speed medium high speed high speed and turbo status 6 MODE Switch Auto Cooling Dry Fan Heating Floor Heating 3D Heating and Space Heating modes for...

Page 10: ...9X25 MA Soleplate of wired controller Q ty 1 3 2 8 8 TIMER Timer setting 9 SWING Set up and down swing status 10 ON OFF Indoor unit On Off 2 5 Simultaneously press and for 5s to enter or cancel the C...

Page 11: ...ler GIA XK46 11 Wired Controller XK46 Edition Two Fig 5 1 2 Parts of wired controller No 1 2 3 4 Name Panel of wired controller Self tapping Screw ST3 9X25 MA Screw M4 25 Soleplate of wired controller...

Page 12: ...e sheathed cord 60227 IEC 52 60227 IEC 53 L 250m L 820 1 5feet 2 0 75 mm 2 2 1 25 mm 2 2 AWG1 8 2 AWG 16 IEC 60227 5 2 007 1 Total length of communication line can t exceed 250m 820 1 5feet 2 The cord...

Page 13: ...s 3 Prohibit installing the wired controller at the place near high temperature objects or water splashing places 4 Prohibit installing the wired controller at the place where faces forward to the win...

Page 14: ...troller can connect to any one indoor unit but the connected indoor unit must be the same series indoor unit The total quantity of indoor unit controlled by wired controller can t exceed 16 sets and t...

Page 15: ...its Please refer to 5 2 3 Parameters Setting 4 When one or two wired controller s control s multiple indoor units at the same time the controlled indoor unit s setting should be the same 5 Wiring of w...

Page 16: ...roller GIA XK46 16 Wired Controller XK46 17 5 1 4 Installation There re two editions of wired controller The Installation way is different Installation way one Fig 5 7 Installation diagram for wired c...

Page 17: ...pair to H1 and H2 wiring column and then fix the screws 5 Set two core into the groove at left side of wiring column and then bundle panel and Soleplate of wired controller together Note If the wire s...

Page 18: ...Master Indoor Unit Under Off status long press MODE button for 5s to set the corresponding indoor unit of wired controller as master indoor unit MASTER icon will be light after finishing setting Note...

Page 19: ...ith an interval of 3 seconds if there are several malfunctions in one indoor unit Timer zone displays present indoor unit project number C5 malfunction of project number conflict Note 1 If master indo...

Page 20: ...project number Timer zone displays current priority operation setting value of indoor unit C07 View indoor ambient temperature Operation method Enter viewing press MODE button in C07 status to enter t...

Page 21: ...olled by the wired controller C12 View outdoor ambient temperature Timer zone displays outdoor ambient temperature C17 View indoor relative humidity 20 90 relative humidity20 90 Operation method Enter...

Page 22: ...After turning on the one button viewing function each wired controller of the entire system will display the project number of its controlling indoor unit on its timer zone The timer zone will displa...

Page 23: ...door Unit Note Under parameter viewing status FAN TIMER SLEEP and SWING buttons are invalid Press ON OFF button to go back to the home page while not to turn on off the unit Under parameter viewing st...

Page 24: ...s master indoor unit MASTER icon will be bright after finishing setting P11 Set infrared receiver of wired controller 00 forbidden 01 activated 01 It can be set only through master wired controller Wh...

Page 25: ...There are two kinds of static pressure level 5 levels 03 04 05 06 07 9 levels 01 02 03 04 05 06 07 08 09 Wired controller can be adapted to the different types of indoor units that it possesses 1 9 l...

Page 26: ...When the temperature unit is F cooling setting temperature minus heating setting temperature 2 F P38 Heating setting temperature under auto mode 16 C 29 C 61 F 84 F 20 C 68 F P43 Set priority operatio...

Page 27: ...Fresh Air Indoor Unit P54 Union setting of Fresh Air Indoor Unit 00 without union control 01 with union control 00 After union function is set Fresh Air Indoor Unit will be turned on off following th...

Page 28: ...turn off the unit The interfaces of On Off status are shown in fig 6 1 6 4 Fig 6 1 Interface of On status in Celsius Fig 6 2 Interface of Off status in Celsius Wired Controller XK46 32 Fig 6 3 Interfa...

Page 29: ...ases or decreases set temperature by 1 C or 1 F holding or button increases or decreases set temperature by 1 C or 1 F every 0 3s In Cooling Fan Heating Floor Heating 3D Heating or Space Heating mode...

Page 30: ...h Air Indoor Unit fresh air indoor unit code FAP will be displayed as shown below Setting temperature won t be displayed and can t be adjusted via or button The air outlet temperature in cooling or he...

Page 31: ...cancel Turbo function Press FAN button to cancel turbo function and start auto speed Note In Dry mode fan speed is low and can t be adjusted When the wired controller is connected with a Fresh Air Ind...

Page 32: ...and HOUR icon is blinking Press or button to adjust timer time Press TIMER button to save the setting and then exit setting Cancel Timer when timer is set press TIMER button to cancel it Timer settin...

Page 33: ...Wired controller GIA XK46 33 Wired Controller XK46 Fig 6 5 Timer Off setting in unit On status in Celsius Fig 6 6 Timer Off setting in unit On status in Fahrenheit...

Page 34: ...it On Off at a certain time can be set through clock timer Set Timer 1 Press TIMER button to enter timer on setting and the ON icon is blinking 2 Press or button to adjust unit On time Press ENTER CAN...

Page 35: ...Wired controller GIA XK46 35 Wired Controller XK46 40...

Page 36: ...Wired controller GIA XK46 36 Wired Controller XK46 41 Fig 6 7 Unit On Off time setting in unit On status in Celsius...

Page 37: ...Wired controller GIA XK46 37 Wired Controller XK46 Fig 6 8 Unit On Off time setting in unit On status in Fahrenheit...

Page 38: ...on status press SWING button to start or stop up down swing 2 When fixed angle swing mode is set in unit on status press SWING button to adjust swing angle circularly as below 2 Left right swing funct...

Page 39: ...Space heating mode Turn on Quiet Function press FUNCTION button to turn to Quiet function and then Quiet icon or auto quiet icon is blinking At this moment press or button to switch between quiet and...

Page 40: ...Wired controller GIA XK46 40 Wired Controller XK46 45 Fig 6 9 Setting of Quiet function in Celsius...

Page 41: ...ction is enabled indoor unit will operate at quiet fan speed Fan speed is lowered so as to reduce the noise of indoor fan motor When Auto Quiet function is enabled indoor unit will change fan speed au...

Page 42: ...ep function is closed while quiet function is still activated Under Auto Fan or Floor Heating mode this Sleep function is not available 6 9 AIR SETTING Air Function Adjust the amount of indoor fresh a...

Page 43: ...Wired controller GIA XK46 43 48 Fig 6 11 Turn on Air Function in Celsius Fig 6 11 or 6 12 Shows how to turn on Air function...

Page 44: ...Wired controller GIA XK46 44 Wired Controller XK46 49 Fig 6 12 Turn on Air Function in Fahrenheit...

Page 45: ...t When unit is on or off press FUNCTION button to select Light function icon will blink Press ENTER CANCEL to turn on the light Turn off the Light When light of indoor unit is on press FUNCTION button...

Page 46: ...Dry modes and setting maximum temperature under Heating 3D Heating and Space Heating modes Thus energy saving can be realized Start up Save function for Cooling When the unit is off simultaneously pre...

Page 47: ...Wired controller GIA XK46 47 Wired Controller XK46 53 Fig 6 14 Save Setting for Cooling in Fahrenheit...

Page 48: ...press TIMER and buttons for 5s to enter into save setting press ENTER CANCEL button to cancel Save function of all modes Note When the Save function is turned on and then set temperature exceeds the...

Page 49: ...CEL function to cancel this setting When Filter Clean Reminder time is up icon will light up to remind you to clean the filer Press FUNCTION button to turn to Filter Clean Reminder Function then press...

Page 50: ...te Description on cleaning level When setting the Filter Clean Reminder Function timer zone will display 2 digits of which the former indicates the pollution degree of operating place and the latter i...

Page 51: ...9 it means the operating time is 5000 hours Heavy Pollution The former digit shows 3 while the latter one shows 0 which indicates the accumulating operating time is 100 hours Each time the latter dig...

Page 52: ...blink Then press ENTER CANCEL button to turn off this function 6 15 REMOTE SHIELD FUNCTION Remote Shield Function Remote monitor or central controller can disable the relevant functions of wired contr...

Page 53: ...cover the operation as state in memory When the card is pulled off or improperly inserted icon will show neither remote control nor operation of wired controller will be effective and icon will be fli...

Page 54: ...Protection FP Malfunction of DC motor b6 Gas liquid separator inlet temperature sensor error E3 Low Pressure Protection FU Compressor 2 Top Temperature Sensor Error b7 Gas liquid separator outlet tem...

Page 55: ...Outlet Pipe Temperature Sensor Error JF Oil return pipe is leaking P3 Protection of Compressor Drive Board Module Reset FE Compressor 4 Current Sensor Error JL Protection of Low High pressure H0 Erro...

Page 56: ...Temperature Sensor Error 65 L8 Power Insufficiency Protection d4 Inlet Pipe Temperature Sensor Error dn Swing Assembly Error L9 Quantity Of Group Control Indoor Units Setting Error d5 Malfunction of...

Page 57: ...or between master control and inverter compressor drive CH Rated capacity is too high Wired Controller XK46 66 Error Code Content Error Code Content Error Code Content U5 Wrong Address of Compressor D...

Page 58: ...it is waiting for debugging A8 Vacuum pumping Mode AJ Filter Clean Reminder A1 Check the compressor operation parameters Ab Emergency Stop AU Remote Urgent Stop A2 After sales Refrigerant Reclaim Ad O...

Page 59: ...C Industria 13 l Pol gono Industrial El Pedregar 08160 Montmel Barcelona Spain Phone 0034 93 390 42 20 Fax 0034 93 390 42 05 info giatsu com www giatsu com...