TTM-000W Series
BA_MA_TTM-00XW_EN_V1.00
33 / 37
9
Other Displays
- - - -
This will be displayed when the input exceeds the upper limit of the display range.
This will be displayed when the thermocouple is disconnected.
This will be displayed when any of ABb terminals of resistance temperature detector is disconnected.
_ _ _ _
This will be displayed when the input drops below the lower limit of the display range.
This will be displayed when DC1-5V 4-20mA input is disconnected.
E r r 0
This will be displayed when memory error occurs.
Repair is required if the error appears again when the power is turned ON.
E r r 1
This will be displayed when the resistance temperature detector is connected while the thermocouple is being
set and when A/D error occurs.
Repair is required if the error appears again when the setting is changed or power is turned ON.
E r r 2
This will be displayed when auto tuning error occurs.
This will be displayed when the user tries to change the parameter while the key is locked.
L o
c
This will be displayed alternately with the normal screen while the auto tuning process is in progress.
A t
This will be displayed when the user tries to change the set value while the control mode is SV2.
5u2
This will be displayed when the user tries to change the set value that is allocated to DI input.
D1
This will be displayed when the user tries to change the setting value at the control mode screen while the
function key is being assigned to RUN/READY.
Fvn
C
This will be displayed when the user tries to change the control mode while the timer is being used.
T1me