E36.0.01.6C-01
Installation and
Operating Manual GIA 0420 … - ex
page 11 of 20
The configuration is done at this point for devices
without option “switching output”. Press
button 1
one more time
after the input of the last parameter to close the configuration menu. The devices restarts (segment test).
5.1 Additional parameter for option / S1
The adjustment of the switching and alarm points follows the filter setting. The following points are added to the
configuration menu:
OVTP
Output function
NO
No output, device used as display
2P
2-point-controller
AL.F 1
Min- / max- alarm, together
Depending on the selected output function further parameters have to be adjusted. The configuration menu
automatically skips parameters not needed for the selected output function. The following diagram shows which
parameters are successively displayed for each output function.
A description of the single parameters follows afterwards.
Parameter
Value
Description
Button 1
Button 2 and 3
1.ON
only at outP =
2P
Switch-on point of output 1
D,.LO
…
D,.X,
Value at which output 1 should be switched on.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
1.OFF
only at outP =
2P
Switch-off point of output 1
D,.LO
…
D,.X,
Value at which output 1 should be switched off.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
1.DEL
only at outP =
2P
Delay of switching function of output 1
0.0
…
999.9
The set value is the time [in seconds] the device waits at least after switching-
off output 1 to switch it on again.
1.ERR
only at outP =
2P
Preferred position of output 1
ON
,
OFF
If an error occurs, the device switches output 1 to “active” (on) or “inactive” (off)
AL.X,
only at outP = A
L.F 1
Max-alarm point
AL.LO
…
D,.X,
Value, at which max-alarm should be triggered.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
AL.LO
only at outP = A
L.F 1
Min-alarm point
D,.LO
…
AL.X,
Value, at which min-alarm should be triggered.
Value has to be between upper and lower measuring range limit set at the
beginning of the configuration menu.
A.DEL
only at outP = A
L.F 1
Alarm delay
0
…
9999
The set value is the alarm delay in seconds.
The alarm case has to last for the set time to trigger the alarm.
After having set and confirmed the last point (depending on the selected output function) the configuration is done.
Press
button 1
one more time after the input of the last parameter to close the configuration menu.
The devices restarts (segment test).