Installation Instructions

 

ELEKTROMAT 
SE 9.15 WS-25,40

 

Model: 10004953 10012

 

 

 
 
 
 
 
 
 
 
 

 

-en- 

 

Status: 26.03.2021

 

 

 

Summary of Contents for 10004953 10012

Page 1: ...f Installation Instructions ELEKTROMAT SE 9 15 WS 25 40 Model 10004953 10012 en Status 26 03 2021...

Page 2: ...2 GfA ELEKTROMATEN GmbH Co KG Wiesenstra e 81 D 40549 D sseldorf www gfa elektromaten de info gfa elektromaten de...

Page 3: ...n 13 8 Emergency manual operation rapid hand chain operator 14 9 Completing commissioning inspection 16 10 Declaration of incorporation Declaration of conformity 17 Symbols Warning Potential injury or...

Page 4: ...d practical experience are what set apart qualified persons They are capable of safely carrying out the tasks involving installation maintenance and modernisation according to the instructions Safe op...

Page 5: ...third parties Warning Danger from improper use of the product Do not let children operate the product unsupervised or use as a toy Warning Danger to life from incorrect installation Work carried out i...

Page 6: ...ight 4000 N Supply voltage 1N 230 V Operating current 3 50 A Operating frequency 50 Hz Power factor cos 0 99 Maximum movement per hour 16 h 1 Class of protection IP 65 Limit switch range maximum revol...

Page 7: ...maximum holding torques or locking torques refer to technical data Connection elements Self locking connection elements with a minimum strength of 800 N mm2 8 8 must be used Utilize the hole diameter...

Page 8: ...8 Mounting Eight threads are provided for mounting Use at least 2 of these Keys are used to connect to the door shaft Use a key that is at least as long as the hollow shaft 8 x M8x16 BAGAD01001_Z002...

Page 9: ...manufacturer must also be observed during installation Warning Potential injury or danger to life During installation be sure to use a lifting device that has a sufficient load carrying capacity Thor...

Page 10: ...t BAGAE01003_Z003 Tighten all connection elements M8 to 25 Nm Install all other connection elements according to the specifications of the door manufacturer BAGAE01006_Z002 25 Nm Secure the keys versi...

Page 11: ...are de energised Observe the applicable regulations and standards Make a proper electrical connection Use suitable tools Performing electrical installation Remove the cover Insert the motor plug Inse...

Page 12: ...12 5 Limit switch adjustment The adjustment of the final limit positions OPEN and CLOSE is described in the instructions for the door control panel...

Page 13: ...ting capacitor M1 Motor X13 Motor plug 7 Limit switch connection F10 Thermal contact S10 Emergency manual operation X12 DES connection 1 Safety circuit 2 Channel B RS485 3 Ground 4 Channel A RS485 5 S...

Page 14: ...ency manual operation must be carried out against the closed brake Warning Danger of the door dropping If you need to apply more than the permissible force of 390N according to DIN EN 12604 DIN EN 124...

Page 15: ...15 Switch on by pulling the red handle Open or close by pulling the chain Switch off by pulling the green handle...

Page 16: ...on cables and cabling for damage or crushing Check that the screw connections and plug connections are fitted properly with a good electric contact Emergency manual operation Check the function with t...

Page 17: ...complies with the provisions of the above mentioned directives Authorised representative to compile the technical documents is the undersigned D sseldorf 10 08 2018 Stephan Kleine CEO Signature The f...

Page 18: ...18...

Page 19: ...19...

Page 20: ...20...