Maintenance and Service
In addition to the usual periodic inspections of the technical systems in accordance with the
regulations and standards valid in this field of application, the catalyst granulate in JRG Coral
force limescale conditioners must be replaced every five years. Georg Fischer JRG offers a
service kit for this purpose. (For the part number, see 'Spare Parts and Service Kit')
The service intervals for granulate change are monitored by an operating hours counter and are
displayed as follows:
10.1
Service Message
This message occurs whenever the service timer reaches 43,800 hours (i.e. 5 years).
When it occurs, replace the catalyst granulate.
Display
The date on which
this message is first
issued is shown in
the 1st column.
Lamp green
HW fault-free: on
Depending on operational state
If HW errors present: off
(E01 – E07)
Lamp red
on
Alarm
on
The alarm can be deactivated by
pressing the appropriate button
Signal contact (BCT)
open
Deactivate/Reset Alarm:
•
To silence the alarm, press the 'Alarm Off' button. The alarm will
sound after a further 48 hours (=2 days) if the fault has still not been
rectified.
•
By holding the Alarm Off button down for 10 seconds, however, you
can disable the alarm long-term (i.e. until the next initialisation). Three
short peeps indicate that deactivation has been successful.
Summary of Contents for JRG Coral force 11000
Page 2: ...Seite 2 von 68 Rev 1113803 1...
Page 15: ...Seite 15 von 68 Rev 1113803 1...
Page 23: ...Seite 23 von 68 Rev 1113803 1 7 2 Filling and bleeding...
Page 24: ...Seite 24 von 68 Rev 1113803 1...
Page 25: ...Seite 25 von 68 Rev 1113803 1...
Page 29: ...Seite 29 von 68 Rev 1113803 1...
Page 30: ...Seite 30 von 68 Rev 1113803 1 8 1 1 Initialisation and Settings Automatic Hygiene Program...
Page 31: ...Seite 31 von 68 Rev 1113803 1...
Page 32: ...Seite 32 von 68 Rev 1113803 1...
Page 33: ...Seite 33 von 68 Rev 1113803 1...
Page 64: ...Seite 64 von 68 Rev 1113803 1 Close filler plug tightly...