4 Working with the master
4.3.4 Type = Temperature
The process is started upon reaching a specific temperature.
Process sequence for hot water (area = hot)
If the hot water becomes colder than the
temperature
(here: 57 °C, still thermally safe
against legionella), then the process starts and opens the valve. If the
temperature
is
exceeded again, the valve closes again (leakage rate). The leakage rate can be defined
separately for each valve.
If the
temperature lower limit
(here: 50 °C) is fallen below, an error message appears
and an entry is made in the error log.
If the
temperature upper limit
(here: 90 °C) is exceeded, an error message appears
and an entry is made in the error protocol. These two limits must be defined mean-
ingfully, since they form the basis for an evaluation of the
.
If the checkmark at
Thermal disinfection (TD)
is set, the parameters shown below it
are displayed and active.
25