Display programme switch DPS and Service push buttons S1, S2
24.3 DPS service menu and service buttons S1/S2 with LEDs
à
Changing to the Service mode is possible in the NA, LS, AU and DO operating modes.
à
If no push button is pressed for 2 minutes in service mode, the control changes automatically to operating mode.
à
In Service mode, the door remains in operation in the current operating mode.
no. DPS Service-LEDs
Parameter
Value
1
ST220 display
Explanation
5
4
3
2
1
1
ef
*
○ ○ ○ ●
Active leaf/passive leaf
00
01
02
1-leaf drive,
2-leaf active
2-leaf passive
2
O h
*
○ ○ ● ○
à
Hold-open time for 1-leaf drives
à
Hold-open time for 2-leaf opening
(with 2-leaf drives)
00
01
… 10 12 … 20 25 … 50 60 s
3
O ®
*
○ ○ ● ●
Hold-open time for 1-leaf opening
(only for 2-leaf drives)
00
01
… 10 12 … 20 25 … 50 60 s
4
Os
*
○ ● ○ ○
Hold-open time for activation with KB
Only applicable for activation from
the closing position of the door.
For activation with SIS during closing,
the hold-open time
Oh
or
O ®
applies.
For activation with KB, after activation
with KI, KA or SIS has already take place,
hold-open time
Oh
or
O ®
applies.
00
01
… 10 12 … 20 25 … 50 60 s
5
O D
*
○ ● ○ ●
Dyn. hold open time extension
00
01
off
on
6
su
*
○ ● ● ○
Delayed closing action GF
00 … 01 …
15
s
2)
16
7
s1
*
○ ● ● ●
Safety 1 contact type
(terminal SIS)
00
02
not used
Normally closed contact
8
f1
*
● ○ ○ ○
Safety 1 function
(terminal SIS)
01
02
03
SIS
SIS and KI
SIS and KA
9
s3
*
● ○ ○ ●
Safety 3 contact type
(terminal SIO)
00
02
not used
Normally closed contact
10
f3
*
● ○ ● ○
Safety 3 function
(terminal SIO)
05
06
SIO stop
SIO stop SF GF (SF and
GF stop with an active
SIO)
11
Te
*
● ○ ● ●
Testing SI1 and SI3
(safety sensors)
00
01
02
No testing
Testing with 24 V
Testing with GND
12
cB
*
● ● ○ ○
Mechanical contact
Contact type
00
01
02
not used
Normally opened contact
Normally closed contact
13
cI
*
● ● ○ ●
Contact sensor inside contact type
00
01
02
not used
Normally opened contact
Normally closed contact
14
a I
*
● ● ● ○
Contact sensor inside
Activation delay time
00
… 01 … 90 × 0,1 s
15
cO
*
● ● ● ●
Contact sensor outside contact type
00
01
02
not used
Normally opened contact
Normally closed contact
16
aa
**
○ ○ ○ ●
Contact sensor outside
Activation delay time
00
… 01 … 90 × 0,1 s
17
e1
**
○ ○ ● ○
Configurable input 1
00
not used
Summary of Contents for TSA 160 NT F