TSA 160 NT Invers at RWA-control panel
19 TSA 160 NT Invers at RWA-control panel
à
Accessory ZR-Invers, mat. no. 090769
à
With 2-leaf drives the power disconnection circuit board from the accessory ZR-Invers is mounted in the pas-
sive leaf drive.
X
Follow the mounting and operating instructions of the SHEV control panel.
X
Setting the parameters:
à
DPS:
Set parameter
a T
to value
0 5
…
0 6
.
à
ST220: Set “Door parameters”, “Drive type” to value “TSA 160 NT Invers” or “TSA 160 NT Z-Invers”.
à
S1, S2: Set parameter 28 to value 05 or 06.
X
Set drive type to 05 or 06 for TSA 160 NT Invers.
à
When the smoke-heat extractor is activated by the SHEV control panel the mains voltage supply to the drive is
interrupted by the mains cut-off printed circuit board.
à
TSA 160 NT Invers opens by means of spring force. With 2-leaf doors, both leaves open.
X
The 24 V alarm output of an RWA control panel is connected to the power disconnection circuit board.
à
The power disconnection circuit board places a load of approx. 35 mA on the RWA control panel.
ALARM
24V
GND
RWA
230V
50Hz
BK
BU
GN/YE
L
N
PE
1
PE
1
3
2
4
BK
BU
GN/YE
BU
BN
DCU5
NTZ1
1
2
BU
BN
1
2
2
1
-
+
1
2
N
L
2
3
9
4
6
7
8
5
T4AH
1
Mains fuse, provided by customer *)
2
Main switch, on site**)
3
Door drive
TSA 160 NT Invers (1-leaf or 2-leaf)
4
Fuse terminal strip, fuse 5×20 mm,
T4AH/250 V AC
5
Ferrite sleeve
6
Earthing base plate
7
Earthing drive hood
8
Mains cut-off printed circuit board
9
Jumper connector from the accessory ZR-Invers
*) The customer must use an on-site automatic cut-out as the line-side disconnecting device, the dimensioning
of which is matched to the type, cross-section, type of routing and ambient conditions of the on site feeder
(at least 6 A, maximum 16 A).
**) Necessary in accordance with EN 60335-1, section 22.2.