TS 4000 R
GB 8
Mounting and securing
6.4 Adjusting door closer
1
Adjustment closer size
2
Adjustment closing speed
X
Adjust closing force (
1
) to match the door width.
X
Set closing speed (
2
).
Closer size
Leaf width a [mm]
1
till 750
2
750 - 850
3
850 - 950
4
950 - 1100
5
1100 - 1250
6
1250 - 1400
Specifications EN 1-6 are applicable only for use with
rods.
à
In accordance with EN directive for fire protection doors, the door closer must be
set at least to size EN 3.
à
Adjustment of closing speed in accordance with EN 1154 (closing time approx. 5 s
from 90° open position).
à
Smooth-moving door must be completely closed by the closer!
à
In combination with guide rails, the door closer size is between EN 1 and EN 3.
Sec
6.5 Mounting cover panel
CAUTION!
X
Do not pinch cable.
X
Attach protective cap in such a way that the smoke switch opening is concealed in the cover to protect
the interior of the system from contamination.
Protective cap must be removed during commissioning of the hold-open device.
Fig.: 6.5.1
X
Clip on cover panel (
1.
).
X
Clip on protective cap (
2.
).
X
Clip on cover cap (
3
.).
X
Bring company logo into readable position and press in flush with the surface (
4
.).
IMPORTANT
Following the guideline for hold-open systems by the DIBt (German Institution for Construction Technology) the
installation of a circuit breaker is compulsory, if door closers with free-swing function are used.
Fig.: 6.4.1