GEZE SecuLogic emergency exit system
7.1.2 Mains connection of the TZ 32x UP variants
The TZ 32x UP variants are protection class II devices, no protective earth conductor is connected.
L
GND
24V
1
3
46
45
42
41
CAN-H
CAN-L
RS485-A
RS485-Β
230 V AC
N
BK
RD
BN
BU
BN
BU
BN
BU
TZ 32x
TST 32x
X3
2
1
3
1
Miniature circuit breaker
2
Lamp-wire connector
3
Power supply
7.1.3 Mains connection of the TZ 32x AP variants
The TZ 32x AP variants are protection class I devices, so connect a protective earth conductor.
X
Perform the protective earth connection test in accordance with VDE 0100 Part 600.
PE
GND
24V
1
3
46
45
42
41
CAN-H
CAN-L
RS485-A
RS485-Β
BK
RD
BN
BU
BN
BU
BN
BU
GN/YE
GN/YE
TZ 32x
TST 32x
X3
L
N
2
1
3
1
Miniature circuit breaker
2
Lamp-wire connector
3
Power supply
7.1.4 Mains connection of the TZ 32x variants in the UP or AP stainless steel box
The TZ 32x variants in the UP or stainless steel box are protection class I devices, so connect a protective earth
conductor.
X
Perform the protective earth connection test in accordance with VDE 0100 Part 600.
PE
GND
24V
1
3
46
45
42
41
CAN-H
CAN-L
RS485-A
RS485-Β
BK
RD
BN
BU
BN
BU
BN
BU
GN/YE
GN/YE
TZ 32x
TST 32x
X3
L
N
2
1
3
1
Miniature circuit breaker
2
Lamp-wire connector
3
Power supply