Storage
11 Storage
RWA emergency power control unit
X
Store the RWA emergency power control unit in a protected location.
X
If the system was already in operation: Disconnect the RWA emergency power control unit from the mains
and from the battery.
Lead batteries
Lead batteries self-discharge during storage. Therefore the following must be observed:
X
Keep storage time as short as possible.
X
Store the batteries or packed RWA emergency power control unit protected against heat at temperatures
below 30 °C.
X
If the system is not used, re-charge batteries every 7 months at the latest.
Recharging batteries
There are 2 possibilities for recharging the batteries:
X
Recharge batteries with a customary battery charger.
– or –
X
Connect the batteries to the RWA emergency power control unit.
X
Insert battery safety fuse.
X
Connect the control panel to the mains.
X
Charge batteries for about 36 hours.
X
Note the new charging date on the batteries.
12 Disposal
All the components of the RWA emergency power control unit have to be disposed of in accordance with
the statutory regulations for hazardous waste.
Batteries contain highly toxic substances and therefore can only be disposed of at collection points prescribed
by law.
Information on the German Battery Act
(Applicable in Germany and all other countries in the European Union, together with the country's own regula-
tions of a separate used battery-return system.)
In accordance with the Battery Directive, we are obliged to inform you of the following in connection with the
sale of batteries or rechargeable batteries respectively in connection with the delivery of devices containing bat-
teries or rechargeable batteries: Rechargeable batteries and batteries must not be disposed of with household
waste. Disposal with household waste is expressly forbidden according to the Battery Directive. As the end-con-
sumer, you are legally obliged to return used batteries. Please dispose of batteries at a municipal collection
point or in store. Batteries obtained from us can be returned to us by mail. The address is: GEZE GmbH, Incoming
Goods, Reinhold-Vöster-Str. 21-29, 71229 Leonberg/Germany.
Batteries which contain harmful substances are identified by a symbol of a crossed-out rubbish bin. The chemical iden-
tifier of the harmful chemical, Cd for cadmium, Pb for lead, Hg for mercury, is located under the garbage can symbol.