Module description
6.6 Weather module WM
Functions:
à
Connections for 1 wind and rain sensor each
à
Wind direction sensor for wind-dependent opening
and closing in case of fire
à
Processing of the signals of external ventilation control units
à
Connections for external signal transfer
1
Operation (green)
2
Fault (yellow)
3
Rain (red)
4
Wind (red)
a
s
f
d
WM
MBZ300
Displays
Symbol
Status
Mode of operation/fault
green, steady light
In operation
red, steady light
Rain sensor active
red, steady light
Wind sensor active
red, flashes slowly
Main wind direction detected
red, flashes rapidly
Triggering threshold for wind sensor
exceeded. Close the window in venti-
lation mode
red, flashes slowly
display on the modules
DM
and
CM
or
SM
respectively
one of them lights up on drive modules
DM
depending
on setting
Wind-direction-dependent opening
and closing of smoke extraction units
(depending on setting) in the RWA case
yellow, steady light
off
Fault (e.g. from wind/rain sensor or
wind direction sensor)
green, flashes rapidly
Fault BUS connection
Changing the wind sensor settings
X
Connect a computer with configuration software via USB.
Wind speed:
X
Adapt the triggering threshold for the wind sensor (set to 2 m/s in the factory).
Wind-direction-dependent opening and closing of smoke extraction units:
X
Adapt the configuration of the control panel to the respective application.