GC 171
Wireless module
183119-01
EN Supplementary sheet
1
Brief description of wireless kit
The wireless kit is part of the GEZE hold-open system FA GC 150 or FA GC 160.
The wireless module GC 171, ID 163051, makes wireless communication possible between the lintel-mounted smoke switch and the
various wireless devices.
à
Wireless ceiling-mounted smoke detector GC 172, ID 159656
à
Wireless ceiling-mounted thermal detector GC 173, ID 159657
à
Wireless input module GC 175, ID 163068 (for the connection of manual trigger switches or contacts for the fire detector system)
2
Wireless module GC 171
2.1 Use
The wireless module GC 171 is connected to the lintel-mounted smoke switch. An alarm triggered at a wireless module is indicated
immediately at the lintel-mounted smoke switch. Interference with a wireless device or a problem with communication is indicated on
the lintel-mounted smoke switch in less than 100 ms.
The wireless module GC 171 forwards wireless signals to the lintel-mounted smoke switch as changes in resistance.
Heed the document for the hold-open system FA GC 150 or FA GC 160 - Instructions for the installation, commissioning, operation
and maintenance, see www.geze.com.
2.2 Technical data
Wireless module GC 171
ID 163051
Colour
RAL 7016 (anthracite grey)
Dimensions (W x H x D)
177 mm x 30 mm x 18 mm
Installation position
Wall assembly
IP rating (in acc. with EN 60529)
IP20, only for dry areas
Ambient temperature
-5°C to 50°C
Input voltage
24 V DC
Input current
Maximum of 15 mA
Number of wireless participants
The wireless module GC 171 can communicate with a maximum of 6 wireless devices.
Signal transfer period
60 s
Antenna
integrated
Frequency range
868.15 MHz to 869.85 MHz
Range
10 m (100 m in space)
Number of frequency channels
7
Modulation technique
FSK (frequency shift keying)
Radiated power
5 dBm (3 mW)
SW2
SW11...SW16
LED11...LED16
LED2
AS
KL1
KL1
SW1
LED1
24V
GND
MRB
AS
1
2
3
4
LED2
PB1
SW2
GC161
GC151
SW2
SW11...SW16
LED11...LED16
LED2
AS
KL1
SW2
SW11...SW16
LED11...LED16
LED2
AS
KL1
KL1
SW1
LED1
24V
GND
MRB
AS
1
2
3
4
LED2
PB1
SW2
GC161
GC151
KL1
SW1
LED1
24V
GND
MRB
AS
1
2
3
4
LED2
PB1
SW2
GC161
GC151
KL1 Connection to the lintel-mounted smoke switch
24 V Supply
GND Supply
MRB Manual trigger switch
AS Ceiling-mounted detector
PB1
Push button for mode selection
“Operating” mode
“Set up wireless connection” mode
LED1x
Wireless device-LEDs
6 LEDs, one LED belongs to one specific
wireless device.
SW1x
Wireless device switch
6 sliding switches, one switch
belongs to one specific wireless device.
LED2
Status LED
Indicates the status of the GC 171.
SW2
Selection of the lintel-mounted smoke switch
OFF = GC 161
ON = GC 151.
2.3 Connection to the lintel-mounted smoke switch GC 151
Lintel-mounted smoke switch GC 151:
X
X
Remove jumper J1.
X
X
Remove jumper J2 (red).
X
X
Set jumper J3 to the measuring chamber (PIN 2-3 with line monitoring).
Wireless module GC 171:
à
The area defined in the following illustration must be kept free.
30
30
5
5
X
X
Set switch SW2 to the ON position.
Use cable type J-Y(ST)Y, 2x2x0.6 mm or 2x2x0.8 mm. Length max. 3 m.
integrier
te
F
estellanlage
Rauchschaltzentr
ale RSZ6
En
er
g
ie
-
versorgung
Sturzmelder mit
A
uslösevorrichtung
Feststell-
vo
rri
ch
tu
n
g
1-
g
. / 2-
g
Funk
modul
GC 171
Decken-
melder
Handaus-
lösetaster
Handaus-
lösetaster
Decken-
melder
Funk
-
decken-
melder
Handaus-
lösetaster
Handaus-
lösetaster
Funk
-
decken-
melder
Funkeingabe
-
modul
GC175
Funkeingabe
-
modul
GC175
J3 J2 J1
Always remove jumpers J1 and J2 from the GC 151.
2.4 Connection to the lintel-mounted smoke switch GC 161
Lintel-mounted smoke switch GC 161:
X
X
DIP1 = ON (with manual trigger switch)
X
X
DIP2 = ON (with ceiling-mounted detector)
X
X
DIP3 = ON (line monitoring to the manual trigger switch)
X
X
Connect KL2.9 to KL2.10 via a 6.8 kΩ resistor
Wireless module GC 171:
X
X
The housing of the wireless module must be at least 7 cm away from the smoke intake openings of the lintel-mounted smoke
switch.
X
X
Set switch SW2 to the OFF position.
Use cable type J-Y(ST)Y, 2x2x0.6 mm or 2x2x0.8 mm. Length max. 3 m.
integrier
te
F
estellanlage
Rauchschaltzentr
ale RSZ6
En
er
g
ie
-
versorgung
Sturzmelder mit
A
uslösevorrichtung
Feststell-
vo
rri
ch
tu
n
g
1-
g
. / 2-
g
Funk
modul
GC 171
Decken-
melder
Handaus-
lösetaster
Handaus-
lösetaster
Decken-
melder
Funk
-
decken-
melder
Handaus-
lösetaster
Handaus-
lösetaster
Funk
-
decken-
melder
Funkeingabe
-
modul
GC175
Funkeingabe
-
modul
GC175
ON
OFF
On GC 161 always set DIP switch 1 to DIP switch 3 to ON.
2.5 “Operating” mode
After the supply voltage has been switched on, the wireless module GC 171 is in “operating” mode.
In “operating” mode the wireless module monitors the set-up wireless connections and signals faults and alarms to the lintel-mounted
smoke switch. Faults and alarms are also indicated on the status LED and the wireless device LEDs of the wireless module. The following
table shows the states for the different events:
à
of the wireless device LEDs of the wireless module,
à
of the status LED of the wireless module,
à
of the LED of the lintel-mounted smoke switch,
à
of the hold-open output of the lintel-mounted smoke switch.
The wireless module indicates an event until the cause has been eliminated. If the cause of an event is no longer present, the wireless
module changes back to normal mode (the displays are deleted and 24 V is applied to the hold-open output of the lintel-mounted
smoke switch again).
Wireless module GC 171
(“operating” mode)
Lintel-mounted smoke switch GC 151
Wireless connection State / fault
Wireless device LED 1x
Status
LED
LED
1)
Hold-open output
KL1: 3-4 / KL3: 1-2
GC 171
Connection quality
green flashes
good
yellow flashes
sufficient
red flashes
poor
off
green
24 V
General fault
off
yellow red
off
0 V
GC 172
GC 173
General fault
red
off
yellow
red
off
0 V
Sabotage
red
off
Loss of connection
red
off
Low battery charge
(warning)
yellow
off
green
24 V
Soiling
(warning)
red/green briefly
Soiling limit reached
red/green long
red
off
0 V
Wireless detector alarm
red
red
red
GC 175
General fault,
broken cable
red
off
yellow
red
off
0 V
Loss of connection
red
off
Low battery charge
(warning
)
yellow
off
green
24 V
Contact (N/O contact) activated,
short-circuit
yellow
yellow
0 V
1) If the LED flashes red 5 x on the lintel-mounted smoke switch GC 161, the 6.8 kΩ resistor has not been connected properly.
Connection quality
If the wireless device switch is in the OFF position during “operating” mode, the corresponding wireless device LED indicates the
connection quality to the corresponding wireless device:
à
LED is off
g
no wireless connection set up
à
LED flashes green every 2 s
g
good connection quality
à
LED flashes yellow every 2 s
g
sufficient connection quality
à
LED flashes red every 2 s
g
still connected but poor connection quality
Connection interference is possible, the quality of the wireless connection should be optimised by changing the position of the
wireless device.
If the wireless device switch is in the OFF position in “operating” mode and the wireless device signals an event (a warning, a fault or an
alarm), the wireless device LED indicates this event in compliance with the table above instead of the connection quality.
General fault
The wireless module signals “general fault” if
à
no wireless connection is set up,
à
the wireless module is in the “set up wireless connection” mode,
à
the set-up switch is in the ON position with GC 172, GC 173 or GC 175,
à
an internal fault has occurred during smoke detection with GC 172
à
the connection between the wireless input module and termination resistor is interrupted with GC 175.
Sabotage
The wireless module signals “sabotage” if a wireless detector GC 172 or GC 173 has been removed from its base.