EN  Supplementary sheet

Brief description of wireless kit

The wireless kit is part of the GEZE hold-open system FA GC 150 or FA GC 160.
The wireless module GC 171, ID 163051, makes wireless communication possible between the lintel-mounted smoke switch and the 
various wireless devices.

 

à

Wireless ceiling-mounted smoke detector GC 172, ID 159656

 

à

Wireless ceiling-mounted thermal detector GC 173, ID 159657

 

à

Wireless input module GC 175, ID 163068 (for the connection of manual trigger switches or contacts for the fire detector system)

Wireless module GC 171

2.1  Use

The wireless module GC 171 is connected to the lintel-mounted smoke switch. An alarm triggered at a wireless module is indicated 
immediately at the lintel-mounted smoke switch. Interference with a wireless device or a problem with communication is indicated on 
the lintel-mounted smoke switch in less than 100 ms.
The wireless module GC 171 forwards wireless signals to the lintel-mounted smoke switch as changes in resistance. 

Heed the document for the hold-open system FA GC 150 or FA GC 160 - Instructions for the installation, commissioning, operation 

and maintenance, see www.geze.com.

2.2  Technical data

Wireless module GC 171

ID 163051

Colour

RAL 7016 (anthracite grey)

Dimensions (W x H x D)

177 mm x 30 mm x 18 mm

Installation position

Wall assembly

IP rating (in acc. with EN 60529)

IP20, only for dry areas

Ambient temperature

-5°C to 50°C

Input voltage

24 V DC

Input current

Maximum of 15 mA

Number of wireless participants

The wireless module GC 171 can communicate with a maximum of 6 wireless devices.

Signal transfer period

60 s

Antenna

integrated

Frequency range

868.15 MHz to 869.85 MHz

Range

10 m (100 m in space)

Number of frequency channels

7

Modulation technique

FSK (frequency shift keying)

Radiated power

5 dBm (3 mW)

SW2

SW11...SW16

LED11...LED16

LED2

AS

KL1

KL1

SW1

LED1

24V

GND

MRB

AS

1

2

3

4

LED2

PB1

SW2

GC161

GC151

SW2

SW11...SW16

LED11...LED16

LED2

AS

KL1

SW2

SW11...SW16

LED11...LED16

LED2

AS

KL1

KL1

SW1

LED1

24V

GND

MRB

AS

1

2

3

4

LED2

PB1

SW2

GC161

GC151

KL1

SW1

LED1

24V

GND

MRB

AS

1

2

3

4

LED2

PB1

SW2

GC161

GC151

KL1   Connection to the lintel-mounted smoke switch 

24 V  Supply  
GND  Supply 

 

MRB   Manual trigger switch 
AS   Ceiling-mounted detector

PB1    

Push button for mode selection 

 

 

“Operating” mode 

 

 

“Set up wireless connection” mode

LED1x  

Wireless device-LEDs

 

 

6 LEDs, one LED belongs to one specific  

 

wireless device.

SW1x   

Wireless device switch

 

 

6 sliding switches, one switch

  

 

belongs to  one specific wireless device. 

LED2   

Status LED

 

 

Indicates the status of the GC 171.

SW2    

Selection of the lintel-mounted smoke switch

 

 

OFF = GC 161 

 

ON = GC 151.

2.3  Connection to the lintel-mounted smoke switch GC 151

Lintel-mounted smoke switch GC 151:

X

X

Remove jumper J1.

X

X

Remove jumper J2 (red). 

X

X

Set jumper J3 to the measuring chamber (PIN 2-3 with line monitoring).

Wireless module GC 171:

 

à

The area defined in the following illustration must be kept free.

30

30

5

5

  

X

X

Set switch SW2 to the ON position.

Use cable type J-Y(ST)Y, 2x2x0.6 mm or 2x2x0.8 mm. Length max. 3 m.

integrier

te

 F

estellanlage

Rauchschaltzentr

ale RSZ6

En

er

g

ie

-

versorgung

Sturzmelder mit

A

uslösevorrichtung

Feststell-

vo

rri

ch

tu

n

g

1-

g

. / 2-

g

Funk

modul

GC 171

Decken-

melder

Handaus-

lösetaster

Handaus-

lösetaster

Decken-

melder

Funk

-

decken-

melder

Handaus-

lösetaster

Handaus-

lösetaster

Funk

-

decken-

melder

Funkeingabe

-

modul

GC175

Funkeingabe

-

modul

GC175

    J3           J2        J1

Always remove jumpers J1 and J2 from the GC 151.

2.4  Connection to the lintel-mounted smoke switch GC 161

Lintel-mounted smoke switch GC 161:

X

X

DIP1 = ON (with manual trigger switch) 

X

X

DIP2 = ON (with ceiling-mounted detector)

X

X

DIP3 = ON (line monitoring to the manual trigger switch)

X

X

Connect KL2.9 to KL2.10 via a 6.8 kΩ resistor

Wireless module GC 171:

X

X

The housing of the wireless module must be at least 7 cm away from the smoke intake openings of the lintel-mounted smoke 

switch.

X

X

Set switch SW2 to the OFF position.

Use cable type J-Y(ST)Y, 2x2x0.6 mm or 2x2x0.8 mm. Length max. 3 m.

integrier

te

 F

estellanlage

Rauchschaltzentr

ale RSZ6

En

er

g

ie

-

versorgung

Sturzmelder mit

A

uslösevorrichtung

Feststell-

vo

rri

ch

tu

n

g

1-

g

. / 2-

g

Funk

modul

GC 171

Decken-

melder

Handaus-

lösetaster

Handaus-

lösetaster

Decken-

melder

Funk

-

decken-

melder

Handaus-

lösetaster

Handaus-

lösetaster

Funk

-

decken-

melder

Funkeingabe

-

modul

GC175

Funkeingabe

-

modul

GC175

ON

OFF

On GC 161 always set DIP switch 1 to DIP switch 3 to ON.

2.5  “Operating” mode

After the supply voltage has been switched on, the wireless module GC 171 is in “operating” mode.
In “operating” mode the wireless module monitors the set-up wireless connections and signals faults and alarms to the lintel-mounted 
smoke switch. Faults and alarms are also indicated on the status LED and the wireless device LEDs of the wireless module. The following 
table shows the states for the different events:

 

à

of the wireless device LEDs of the wireless module,

 

à

of the status LED of the wireless module, 

 

à

of the LED of the lintel-mounted smoke switch,

 

à

of the hold-open output of the lintel-mounted smoke switch.

The wireless module indicates an event until the cause has been eliminated. If the cause of an event is no longer present, the wireless 
module changes back to normal mode (the displays are deleted and 24 V is applied to the hold-open output of the lintel-mounted 
smoke switch again). 

Wireless module GC 171

(“operating” mode)

Lintel-mounted smoke switch GC 151

Wireless connection State / fault

Wireless device LED 1x

Status

LED

LED

1)

Hold-open output 

KL1: 3-4 / KL3: 1-2

GC 171

Connection quality

green flashes 

 good

yellow flashes 

 sufficient

red flashes 

 poor

off

green

24 V

General fault

off

yellow red

off

0 V

GC 172

GC 173

General fault

red

off

yellow

red

off

0 V

Sabotage

red

off

Loss of connection

red

off

Low battery charge

(warning)

yellow

off

green

24 V

Soiling 

(warning)

red/green briefly

Soiling limit reached

red/green long

red

off

0 V

Wireless detector alarm

red

red

red

GC 175

General fault,

broken cable

red

off

yellow

red

off

0 V

Loss of connection

red

off

Low battery charge

(warning

)

yellow

off

green

24 V

Contact (N/O contact) activated,

short-circuit

yellow

yellow

0 V

1) If the LED flashes red 5 x on the lintel-mounted smoke switch GC 161, the 6.8 kΩ resistor has not been connected properly.

Connection quality

If the wireless device switch is in the OFF position during “operating” mode, the corresponding wireless device LED indicates the 
connection quality to the corresponding wireless device: 

 

à

LED is off  

 

 

no wireless connection set up

 

à

LED flashes green every 2 s  

good connection quality

 

à

LED flashes yellow every 2 s  

sufficient connection quality

 

à

LED flashes red every 2 s   

still connected but poor connection quality

Connection interference is possible, the quality of the wireless connection should be optimised by changing the position of the 
wireless device.
If the wireless device switch is in the OFF position in “operating” mode and the wireless device signals an event (a warning, a fault or an 
alarm), the wireless device LED indicates this event in compliance with the table above instead of the connection quality.

General fault

The wireless module signals “general fault” if 

 

à

no wireless connection is set up,

 

à

the wireless module is in the “set up wireless connection” mode,

 

à

the set-up switch is in the ON position with GC 172, GC 173 or GC 175,

 

à

an internal fault has occurred during smoke detection with GC 172

 

à

the connection between the wireless input module and termination resistor is interrupted with GC 175.

Sabotage 

The wireless module signals “sabotage” if a wireless detector GC 172 or GC 173 has been removed from its base.

Reviews: