22
Group address Table on three levels:
KNX 3 Level Structure
Value DMX512
Chan-
nel Nr.
Se-
quence
Nr.
KNX-DMX Gate-
way Function
Detail
Main
Groups
MG
UG
0-15
(S1)
0
0-255 0..255 001-256 -
DPT 5.001 transmits 1byte
value (Absolute value)
1 Byte value is stored
into the corresponding
DMX-Channel directly
0-15
(S1)
1
0-255 0..255 257-512 -
DPT 5.001 transmits 1byte
value (Absolute value)
0-15
(S1)
2
0-255 0/1
001-256 -
DPT 1.001 value
transmission
When a 1 is received
the value stored in
sequence Nr. 8 is sent
to the correspond-
ing DMX-Channel
When a 0 is received
the DMX-Channel
is turned off.
0-15
(S1)
3
0-255 0/1
257-512 -
DPT 1.001 value
transmission
0-15
(S1)
4
0-255 -7..+7 001-256 -
DPT 3.007 value
transmission
Relatively lighter or
darker dimming than
the current level
0-15
(S1)
5
0-255 -7..+7 257-512 -
DPT 3.007 value
transmission
0-15
(S1)
6
0-7
0/1
ALL
0-7
DPT 1.001 value
transmission
Access saved sequences
The selected sequence
values of all 512 chan-
nels are transmitted
on the DMX512 bus
0-15
(S1)
6
8-15
0/1
ALL
0-7
DPT 1.001 value
transmission
Save the new sequence
All current DMX values
in channels 1-512 are
stored in the selected
sequence position
0-15
(S1)
6
16
0/1
ALL
-
DPT 1.001 value
transmission
All channels central on
All 512 channels
display 100% when
1 is transmitted, 0%
when 0 is transmitted
0-15
(S1)
6
17
0..255 ALL
-
DPT 5.001 value
transmission
Repetition rate parameters
Repetition rate
of 10msec
Value default 3
0-15
(S1)
6
18
0..7
ALL
-
DPT 3.007 value
transmission
Set downward dim-
ming curve
Dim repitition value
Value Default 15=1%
0-15
(S1)
6
19
0..7
ALL
-
DPT 3.007 value
transmission
Set upward dimming curve
Dim repitition value
Value Default 15=1%
0-15
(S1)
6
20
0/1
ALL
-
DPT 1.001 value
transmission
Deactivate auto-
matic dimming
Disables auto-
matic dimming
when value = 0