4 Parameter settings
BU 0510 EN
technische Änderungen vorbehalten
29
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P434
Relay 1 function (K1)
P
Control terminals 1/2:
The settings 3 to 5 and 11 work with 10% hysteresis, i.e. the
relay contact closes (fct. 11 opens) when the limit value is reached and opens (fct. 11
closes) when a 10% smaller value is undershot. This behaviour can be inverted with a
negative value in P435.
0 ... 38
[ 1 ]
Setting / Function
Relay contact ...
for limit value or
function
(see P435)
20:
Reference
Closes
21:
End position
Closes
22:
Position
Closes
23:
Absolute position
Closes
24:
Absolute position array
Closes
25:
= Position (Comparison position)
Closes
26:
= Absolute position
(
Comparison absolute position)
Closes
Attention:
The standardisation assigned to Output 1 in parameter P435 is
deactivated with PosiCon relevant functions (20-26, see
parameterisation function Output 1, P434).
The hysteresis assigned to Output 1 in parameter P436 is deactivated
with PosiCon relevant functions (20-26, see parameterisation function
Output 1, P434). The parameterisation of the hysteresis can be
parameterised jointly using parameter P625 for all outputs with reference
to the functions relevant to PosiCon.
P441
Relay 2 function (K2)
P
0 ... 38
[ 7 ]
Control terminals 3/4:
Functions are identical to P434!
P450
Relay 3 Function (DOUT1)
SK 520E
P
0 ... 38
[ 0 ]
Control terminals 5/40:
Functions are identical to P434! Digital output, 15V to DGND.
P455
Relay 4 function (DOUT2)
SK 520E
P
0 ... 100 %
[ 10 ]
Control terminals 7/40:
Functions are identical to P434! Digital output, 15V to DGND.
P470
Digital input 7
SK 520E
0 ... 62
[ 0 ]
No function
as factory setting, control terminal 27 (DIN7)
Es können unterschiedliche Funktionen programmiert werden. Diese sind der folgenden
Tabelle zu entnehmen. Funktionen sind identisch mit P420...P425!