background image

**Effective Intensity Requirements for Sleeping Area

Visible Notification Appliance

Distance from Ceiling to Top of Lens

Intensity

greater than or equal to 24" (610mm)

110 Cd

less than 24" (610mm)

177 Cd

GXS REMOTE STROBE

UL 1971 COMPLIANT

Installation Instructions-Owner's Information

I. INTRODUCTION

The Gentex model GXS Remote Strobe is a high quality remote visible signaling appliance. The

high-intensity strobe utilizes a Xenon flash tube which generates a high-intensity light, visible

from all sides of the lens. The GXS Remote Strobe is intended to provide a visible notification

signal for the purpose of life safety and property protection. This appliance is ideal for hotels,

apartments, hospitals, rest homes or wherever dependable visible alarms are required. This

appliance is listed in compliance with UL 1971, Signaling Appliances For The Hearing Impaired.

II. LOCATION

This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with

this installation manual, the recommendation of the local authorities having jurisdiction, and other

NFPA Standards that provide standards on notification appliances for protective signaling

systems. The Gentex GXS Remote Strobe is intended for indoor installation only and is not

listed for outdoor or drip proof applications.

Wall-mounted appliances shall have their bottoms at heights above the finished floor of not less

than 80 in. (2m) and no greater than 96 in. (2.4m)**. Spacing shall be in accordance with Table

A. If a room configuration is not square, the room size that will entirely encompass the room or

subdivide the room into multiple squares shall be used.

WARNING!

Visual signal must be in the direct viewing area of the occupant in order to be seen.

WARNING!

Visual signal can not be seen when objects such as doors, furniture or walls block

visual signal.

NOTICE:

Visual signals for the hearing impaired are only one method of alerting the hearing

impaired. Visual signals may not be the preferred method for notifying all hearing

impaired individuals.

For a period of 36 months from the date of purchase, or a maximum of

42 months from the date of manufacture, Gentex warrants to you, the

original purchaser, that your appliance will be free from defects in

workmanship, materials, and construction under normal use and

service. If a defect in workmanship, materials, or construction should

cause your appliance to become inoperable within the warranty period,

Gentex will repair your appliance or furnish you with a new or rebuilt

replacement appliance without charge to you except for postage required

to return the appliance to us. Gentex will not reimburse you for repairs or

replacement parts provided by other parties. Your repaired or replace-

ment appliance will be returned to you free of charge and it will be cov-

ered under this warranty for the balance of the warranty period.

This warranty is void if our inspection of your appliance shows that the

damage or failure was caused by abuse, misuse, abnormal usage, faulty

installation, improper maintenance, or repairs other than those performed

by us.

ANY WARRANTIES IMPLIED UNDER ANY STATE LAW,

INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR

FITNESS FOR A PARTICULAR PURPOSE, APPLY ONLY FOR THE

WARRANTY PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT

SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN

IMPLIED WARRANTY LASTS, SO THE ABOVE EXCLUSION MAY NOT

APPLY TO YOU.

GENTEX WILL NOT BE LIABLE FOR ANY LOSS, DAMAGE,

INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND

ARISING IN CONNECTION WITH THE SALE, USE OR REPAIR OF

THIS APPLIANCE. THE MAXIMUM LIABILITY OF GENTEX SHALL

NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU

FOR THE APPLIANCE. PLEASE NOTE THAT SOME STATES DO NOT

ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CON-

SEQUENTIAL DAMAGES, SO THE ABOVE EXCLUSION MAY NOT

APPLY TO YOU.

If a defect in workmanship, materials, or construction should cause

your appliance to become inoperable within the warranty period, you

must return the appliance to Gentex postage prepaid. You must also

prove to the satisfaction of Gentex the date of purchase of your

appliance. Warranty service may only be performed by Gentex

personnel at Gentex's facilities in Zeeland, Michigan. You must also pack

the appliance to minimize the risk of it being damaged in transit. You

must also enclose a return address. Appliances returned for

warranty service should be sent to: Gentex Corporation, 10985 Chicago

Drive, Zeeland, MI 49464. If we receive an appliance in a damaged

condition as the result of shipping, we will notify you and you must file a

claim with the shipper.

THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU

MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO

STATE.

GENTEX CORPORATION

10985 CHICAGO DRIVE, ZEELAND, MI 49464

PHONE: 800-436-8391

www.gentex.com

550-101-T

6-1-93

LIMITED WARRANTY

Note:

AC Voltage Range Limits: 96-132v. This product was only tested to the stated voltage

range; do not apply 80% and 110% of this range for system operation.

NA = Not Allowable

Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to

serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are

complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. The materials do not address all

legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations

and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules.

Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice.

Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.

WARNING! Visual signal must be installed within 16 feet of the pillow when

used in a sleeping area.

REMOTE VISIBLE SIGNALING APPLIANCE

Table A

VI. CLEANING AND MAINTENANCE

Each notification signaling appliance should be maintained in reliable operating condition.

Periodic inspections and tests should be made to assure proper operation of the appliances.

Visible appliances may require periodic cleaning to remove dust or debris that may have

accumulated on the appliance. The frequency of cleaning will depend on the local ambient

conditions.

VII. TO RETURN A GXS REMOTE STROBE UNIT

Should you experience problems with your GXS Remote Strobe unit, proceed as follows.

1. Turn off electrical power to the auxiliary alarm circuit.

2. Unscrew the unit from the electrical box.

3. Disconnect the unit from the field wiring. Reconnect the two hot supply voltage circuits (black

wires) and the two neutral supply voltage circuits (white wires) for AC Models of the auxiliary

alarm circuit to maintain power to the other auxiliary alarm appliances in the system.

4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential

damage due to shipping or mishandling). Include your return address and complete details

as to the nature of the difficulties being experienced and date of installation.

5. Return to: Gentex Corporation, 10985 Chicago Drive, Zeeland, MI 49464. Prior to returning,

call the Gentex field service department at 1-800-436-8391 or e-mail [email protected]

for a RMA number.

VIII. ELECTRICAL SPECIFICATIONS

WALL STROBE CURRENT RATINGS

Candela

Regulated 120VAC

Max. Operating Current(mA)

177

209

550-0101

Page 1

Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2007 Edition

Maximum Room Size

Minimum Required Light Output ( Effective Intensity, Cd)

Meters

Feet

One Light per

Room

Two Lights per Room

(Located on Opposite Walls)

Four Lights per Room (One

Light per Wall)

6.10 x 6.10

20 x 20

15

NA

NA

8.53 x 8.53

28 x 28

30

Unknown

NA

9.14 x 9.14

30 x 30

34

15

NA

12.2 x 12.2

40 x 40

60

30

15

13.7 x 13.7

45 x 45

75

Unknown

19

15.2 x 15.2

50 x 50

94

60

30

16.5 x 16.5

54 x 54

110

Unknown

30

16.8 x 16.8

55 x 55

115

Unknown

28

18.3 x 18.3

60 x 60

135

95

30

19.2 x 19.2

63 x 63

150

Unknown

37

20.7 x 20.7

68 x 68

177

Unknown

43

21.3 x 21.3

70 x 70

184

95

60

24.4 x 24.4

80 x 80

240

135

60

27.4 x 27.4

90 x 90

304

185

95

30.5 x 30.5

100 x 100

375

240

95

33.5 x 33.5

110 x 110

455

240

135

36.6 x 36.6

120 x 120

540

305

135

39.6 x 39.6

130 x 130

635

375

185

Page 4

THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES

FREQUENTLY CAUSE POWER INTERRUPTIONS, GENTEX SUGGESTS YOU DISCUSS

FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.

Reviews: