EXPLOSION-PROOF SWITCHGEAR BOX 

TYPE: 

X450DA2/d

 

N740058 

– 4rd edition 

Valid from: 

28.1.2020 

Tel.: +4220583221500, Fax: +420583214183

 

 

GENERAL 

This User’s Manual has been drawn up in accordance with: 

 

Technical  requirements  for  equipment  and  protective  systems 
intended 

for 

use 

in 

potentially 

explosive 

atmospheres 

(2014/34/EU).

 

 

Technical  requirements  for  products  from  the  point  of  their 
electromagnetic compatibility 

(2014/30/EU).

 

 

 

 

 

 

SAFETY GUIDELINES AND IMPROPER USE 

Do not leave this User’s Manual in the switchgear box during 
operation! 

 

Do  not  operate

  X450DA2/d 

switchgears  in  SNM 

mine  areas

 

(SNM3)

  according  to  ČBÚ  Decree  No. 

22/1989  Coll., 

or  in  explosive  atmospheres

 

(hazardous conditions 1)

 according to ČSN EN 1127-2. 

 

Do  not  operate  X450DA2/d  switchgears  in  Zone  0 
explosive gas atmospheres (ČSN EN 60079-10-1) and 
Zone 20 and 21 explosive dust atmospheres (ČSN EN 
60079-10-2) 

 

The cable glands must always be in the 

Ex “d”

 design 

(flame-proof enclosure) according to ČSN EN 60079-1 

 

In  the  case of  cable  entry  through  cable  glands  with  a 

sealing ring

, only use 

compact

 and 

round

 cables with 

sheathing  made  of 

thermoplastic

thermoset

  or 

elastomeric  materials

.  The  bedding  and  sheathing 

must  be 

extruded

  and  the  bedding  material,  if  used, 

non-absorbent. The 

cable

 must be at least 

3 m long

!

 

 

There  may  be 

parts  with  hot  surfaces,  i.e. 

hazardous  temperature  inside

  the  X450DA2/d 

switchgear.

  Open  the  switchgear  only  in  the 

absence  of  explosive  atmospheres  and  in  a  non-
voltage  state  after  a  sufficient  time  since  its 
deactivation

 to allow the hot parts to cool. 

 

X450DA2/d  switchgears  are  not  designed  for  non-
professional use. 

Installation, start up and any service 

whatsoever  must  be  performed  by  workers  with 
professional  expertise  and  in  conformance  with  safety 
regulations. 

 

Operate

  X450DA2/d  switchgears  in  accordance  with 

the  following  operating  conditions,  technical  and  label 
data. 

 

Do  not  replace  the  existing  internal  equipment  of 
the  switchgear  with  equipment  inconsistent  with 
the  documentation  supplied  with  the  product

  (e.g. 

replacement  of  an  existing  6A  circuit  breaker  with  a 
10A circuit breaker). 

 

If  the  switchgear  contains  a 

current  protector

regularly  verify  their  function  at  least  every  6 
months

  using  the  test  button  (while  observing 

applicable safety regulations). 

 

Some 

mining cables (e.g. type CBEH)

 have individual 

wires provided with a semi-conductive removable layer. 

Always  remove  this  layer

  before  connecting  the 

wires!  

 

Switching  and  protective  devices  inside  switchgears 
may 

produce 

short-term 

electromagnetic 

interference

  and  therefore  have  to  be  used  in 

industrial  zones,  where  they  do  not  have  a  negative 
impact on other equipment. 

 

Carry  out  storage,  transport,  assembly,  installation, 
revision  and  preventive  maintenance,  repairs  and 
service  in  accordance  with  the  instructions  stated 
hereunder.  

1.  USE 

Switchgears  X450DA2/d  are  designed  primarily  for  installation  in 
mines containing methane, in areas with explosive gas atmospheres, 
in  areas  with  explosive  atmospheres  with  flammable  dust  and  areas 
with a risk of fire or explosion of explosives. 

2.  OPERATING CONDITIONS 

2.1.  External  influences

  in  accordance  with

 

ČSN  33  2000-5-51

 

– 

Category A: 

ENVIRONMENT 

Code 

Description of external influence 

Specification 

AA 

Ambient temperature Ta 

-20 °C to +40°C 

AB 

Atmospheric humidity 

up to +30°C .. 

100% 

up to +40°C ... 

70% 

AD4 

Presence of water 

spraying water 

AE4 

Presence of foreign solid particles 

light dustiness 

AF4 

Presence of corrosive substances or 

contaminants 

permanent 

AG3 

Impact 

strong (20J) 

AH 

Vibrations 

see Article 6 – 

Revision 

 
2.2.  External  influences

  in  accordance  with

 

ČSN  33  2000-5-51

 

– 

Category B: 

USE 

Code 

Description of external influence 

Specification 

BE3N1 

Risk of explosion of combustible dust 

see section 

2.4 

BE3N2 

Risk of explosion of flammable gases and 

vapours 

see section 

2.4 

BE3N3 

Risk of explosion of explosives 

see section 

2.4 

BA5 

Skills of persons 

knowledgeabl

e persons 

BC3 

Contact of persons with earth potential 

frequent 

 

2.3.  Unspecified  external  influences  are  normal

  in  accordance 

with ČSN 33 2000-5-51.

 

 

2.4.  Use in areas and atmospheres in accordance to installation 

regulations 

Areas 

Standard name (version) 

Standard 

SNM 

(SNM0,SNM1, 

SNM2) 

ČBÚ Decree 

(version 

I M2

ČBÚ No. 22/1989 

Coll., 

s. 232, s. 233 

ČBÚ No. 75/2002 

Coll., 

Explosive 

atmospheres 

(hazardous 

conditions 2) 

Explosive atmospheres – 
Explosion prevention and 
protection – Part 2: Basic 

concepts and methodology 

for mining. 

(version 

I M2

ČSN EN 1127-2 

ZONE 1, 2 IIA, 

IIB 

Explosive atmospheres 

– Part 10-1: Classification of 

areas 

– Explosive gas 

atmospheres (version 

II 

2G/3D

ČSN EN 60079-10-1 

ZONE 22 IIIA, 

IIIB T>71°C 

Explosive atmospheres 

– Part 10-2: Classification of 

areas 

– Explosive dust 

atmospheres 

(version 

II 2G/3D 

1)

 

ČSN EN 60079-10-2 

V1, V2 

Regulations for electrical 

equipment in areas with a 

risk of fire or explosion of 

explosives 

ČSN 33 2340 

1)

 

The device is designed for fixed installation, where the installation 
is  supposed  to  minimize  the  risk  of  electrostatic  discharge  –  see 
EN TR 50 404 a IEC/TS 60 079-32. 

 