Figure 107:
SENSORMANAGER II Status Site
7.3.4
Configuration
The SENSORMANAGER II provides the opportunity of the definition of pre-alarm-thresholds.
Beside the name of the input you also define here as shown above the alarm thresholds, the
sensor range and the measurement unit. Note, that the alarm values (low and high) are only
active if the fields beside the alarm value
s are enabled. In the drop down menu “Sensor Type”
some basic sensor models are already listed, which you can choose to set predefined values
for these types (select “Custom” to make divergent or individual settings).
You can calibrate every sensor with the Sensor Range, that means if you want to rise a
measured value for 5°C, just modify the default range from 0-100 to 5-100. Therefore you are
able to adjust the measurement values like a gauged thermometer.
With the field “Hysteresis” you define the scope within the defined value can oscillate without
releasing an alarm. This is important e.g. for temperature measurements, which are not
increasing/decreasing continuously.
At “Lograte” you can set the loop time (in sec) in which the measured values will be written into
the logfile.
Figure 108:
SENSORMANAGER II Configuration Analog Inputs