Model 1042LH Humidifier Installation Manual

7. Connect drain hose to 5/8" spout on humidifier cabinet

using hose clamp provided.  Run 5/8" hose to suitable
drain such as floor drain, laundry sink or to a condensate
pump (sold separately).  Be sure hose has continuous
slope and is not kinked at any point.

8  Turn on water supply and check operation of humidifier.  

Set humidistat to a demand setting.  With the furnace off, 
the solenoid valve should be closed.  Start the furnace, 
the solenoid valve should open when the blower or 
burner circuit is energized.  Check flow of water through 
distributor trough and evaporator pad.  The standard 

GF-

9903776 orifice will supply approximately

 

3.5 GPH of 

water at a line water pressure of 60 PSI.  For

 

low water 

pressures (20-40 PSI) a larger orifice 

GF-

9903775 is 

available to provide the same flow.  Leave

 

humidistat set 

at the recommended setting.

Installation Final Steps

How The Humidifier Works

The operating principle of the humidifier is based on the most efficient and economical means of
evaporating water to the air.  The humidifier uses only 2.5 watts of electrical power during operation, less
than the smallest household light bulb.  The heat necessary for evaporating water is produced by the
furnace.  The water supply to the humidifier is controlled by the electric solenoid valve.  The humidistat
connected in series with the solenoid provides low voltage control of the humidifier.  The humidistat is
designed for wall mounting in the living area or surface mounting on the return air duct.

Water flows through a strainer, is metered through an orifice to provide the proper amount of water, and is
supplied to the Vapor Pad

®

 by the distributor trough.  Approximately 200

CFM of air is by-passed from the warm air plenum through the humidifier
and returned to the cold air plenum.  Moisture is evaporated to the air
passing through the evaporator pad. 

Minerals are not blown into the air stream as occurs in atomizing
humidifiers; they are left on the evaporator pad where a high percentage
is carried off with the waste water.

When the humidifier is installed and operating, no adjustments are
necessary other than setting the control knob on the humidistat to the
desired level of humidification.  Set knob on the humidifier to "OPEN"
position. To turn the humidifier off, close the water supply valve, switch
electrical power off and turn the humidistat off.  If furnace is used for
summer cooling or ventilating set air damper on "CLOSED".

CAUTION

:  

Do not set relative humidity too high during cold weather.  Excessive humidity may cause

condensation on windows or in walls.  Refer to recommended settings as described in the humidistat
owners manual.

At Outside 

Temperature

Recommended 

Setting

-20°F

-29°C

15%

-10°F

-23°C

20%

0°F

-18°F

25%

+10°F -12°C

30%

+20°F

-7°C

35%

+30°F

-1°C

40%

!

Our Brands

®

Last Updated:  

05

-202

1

400 Midwest Rd. 

Toronto, ON M1P

 

3A9 

Canada

 

Toll Free:  (888) 216-9184

 

www.

generalaire

iaq

.ca

 

sales@

G

eneral

A

ire

IAQ

.c

a

Summary of Contents for GF-1042DMM

Page 1: ...or residential installation only Commercial installation voids warranty Modification or alteration of product parts installation instructions or local safety codes voids warranty Read our full warrant...

Page 2: ...INSTRUCTIONS Failure to heed them can result in serious injury or death CAUTION This symbol indicates IMPORTANT INSTRUCTIONS Failure to heed them can result in serious injury or material property dama...

Page 3: ...relay Model GF GA50 Specifications Model GF 1042DMM Legacy Flow Through Humidifier Type Flow Through GPD 17 Based on 120 F 49 C Plenum Temperature Warranty Years 5 Replacement Vapor Pad GF 990 13 Repl...

Page 4: ...r trough 3 Install connecting collar Connect by pass pipe to collar and humidifier cabinet Using holes at top and bottom of humidifier bypass opening screw by pass pipe to humidifier cabinet Top Of Te...

Page 5: ...ing and close saddle valve 8 Turn handle counterclockwise to open saddle valve leave open for several seconds to flush dirt from pipe and tubing Steel Brass or Hard Plastic Pipe 1 Shut off water suppl...

Page 6: ...ase to seal off air entering through the vents Low voltage wire may enter the humidistat under the foam seal 5 Connect wires to screw terminals on the control assembly as shown in wiring diagram Repla...

Page 7: ...oid provides low voltage control of the humidifier The humidistat is designed for wall mounting in the living area or surface mounting on the return air duct Water flows through a strainer is metered...

Page 8: ...brass strainer body from the solenoid valve Carefully pull the strainer screen GF 990 17 from the orifice fitting Clean the mineral deposits from all parts If the orifice is clogged it may be opened...

Page 9: ...the greatest production of moisture Check the setting of your humidistat to ensure it is set higher than current humidity levels in your home when in doubt turn it all the way to the right at maximum...

Page 10: ...d the pad becomes ineffective This reduces the output of the humidifier and increases water consumption Replace the Vapor Pad annually 5 Why would I want to install a humidifier For many reasons 1 Sin...

Reviews: