background image

15

Elite Steam 

+03U221903

 REV 

2.

1

Fig. 3.w

Fig. 3.x

3.6.1   Connect the E2 Humidistat for On/Off Operation:
1. Remove the humidistat from the base, squeeze the louvered base at the top and bottom. To remove the humidistat from the wall, 

     lift up on the humidistat and pivot top away from wall.

2. Before wall mounting, please remove the black foam gasket.

3. Before return air duct mounting, please remove the breakout piece.

4. If return air duct mounting, route wires between humidistat and base.

5. Mount the sensor outside the house. Do not mount on South side of the house or in direct sunlight. Place at least 4 feet away 

    from any exhaust vent. If in air intake, place 1 foot or closer to outside wall. Place at least 6” higher than possible snow. Do

    not route sensor wire near high voltage wires.

6. Connect the GND-IN terminals on the humidifier to the HUM terminals on the E2 Humidistat. Connect the GND-24V terminals

    to the ACL-ACN terminals on the E2 Humidistat. see Fig.3.x

3.6.2 Modulating Operation

Connect an external 0...10 Vdc modulating input between terminals IN-GND.

Connect any S

afety Switches (high-limit, air fl

ow switch, remote on/off) in series to 

terminals AB-AB. If no safety switches are used, then a jumper must be installed between

AB-AB. DO NOT apply any voltage to AB-AB. 

3.6.3 Connect  the ADCD humidistat for Modulating Operation

To select signal modulating see Fig 3.y

Connect the power supply to the ADCD  G and G O terminals, using the terminal GND and 24V 

on the Elite Steam.

Connect an external signal to the ADCD using the terminal IN from the Elite Steam  and AOUT in 

ADCD.

E2  HUMIDISTAT

ADCD HUMIDISTAT

See the diagram below.

3.6.4 Safety and High Limit Switches

Remove the jumper between terminals AB-AB and connect any simple high-limits, air flow switch, 12500 pressure switch, 

and remote contacts in series to terminals AB-AB; otherwise, if no such dry contacts are available, the jumper 

must remain in place between terminals AB-AB.  DO NOT apply any voltage to AB-AB.
Thread the control wiring through the bottom of the unit, and the strain relief (see photo at top of 

previous page), and then up the side of the control module to the top right wiring terminal blocks.

Connect the control wiring to the control wiring terminal blocks found at the top right side of the control 

module.

EXTERNAL

REGULATOR

Elite Steam

ON          DIP

1    2    3    4

ADCD

DIP SWITCH SETTNGS

FOR HUMIDISTAT ONLY OPERATION

ON

OFF
OFF

ON

P R E S S U R E

S W I T C H

N2

GND
N1
AB
AB
GND
IN

NO

C

NC

C
NO

GND
24V

AC L

AC N

HUM

SNSR

OUTDOOR TEMP. SENSOR

  (not used in manual mode)

Fig. 3.y

ADCD

Summary of Contents for Elite Steam DS15

Page 1: ...Residential Steam Humidi ers User manual Elite Steam...

Page 2: ...03U221903 REV 2 1 REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING LATCH THE CYLINDER CLAMP REMOVE BEFORE INSTALLING Warning If present remove the fo...

Page 3: ...BEFORE beginning installation Check for shipping damage to cartons Mark the shipping waybill accordingly Open cartons and check for any hidden damage Mark the shipping waybill accordingly Check packi...

Page 4: ...4 Elite Steam 03U221903 REV 2 1...

Page 5: ...sic Operation 11 9 14 17 17 17 17 5 OPERATING ELITE STEAM 5 1 Displaying Information 5 2 Changing The Maximum Production 18 5 3 Activating Manual Drain 18 5 4 Resetting the Hour Counter 18 5 5 Using t...

Page 6: ...oo much as the water fills the cylinder the drain valve 13 will be activated to drain away some water and reduce the current flow to acceptable levels Note that any time the drain valve is activated t...

Page 7: ...ife will be accompanied by the need to replace filter elements with each cylinder change Humidity load demands have an effect on cylinder life Normal installations where humidity capacity is properly...

Page 8: ...lons per day 12 Lbs per hour 220 240v Humidifier only Kit selection required Duct steam injection 15 gallons per day 5 5 Lbs per hour 115 120v Duct steam injection 35 gallons per day 12 Lbs per hour 2...

Page 9: ...mm 6 E 24 m m 0 0 6 F max 0 2 Degrees Tab 3 a Millimeters Inch A B C Kilograms Pounds Weight empty Weight packaged Weight installed with water Tab 3 c Duct Steam Injection Room Steam Discharge Unit D...

Page 10: ...102 4 600 23 5 8 35 1 3 8 69 2 3 4 48 4 0 1 5 8 5 0 2 23 7 8 3 0 1 1 8 1 7 8 61 2 3 8 16 5 8 70 2 3 4 65 21 2 60 2 3 8 23 7 8 94 3 5 8 81 31 4 50 2 9 3 8 54 21 8 24 7 8 40 1 5 8 Fig 3 f 3 2 2 Fasteni...

Page 11: ...and conductivity of water Water Conductivity must be matched by specifications of the steam cylinder Check or know the water conductivity of the proposed site before installation Replace the steam cy...

Page 12: ...ple fact when running the steam hose steam naturally flows uphill and condensate naturally flows downhill Run the steam hose or piping to avoid any kinks sharp elbows or low spots that could collect t...

Page 13: ...ings show the minimum recommended distances to avoid the flow of humidified air from coming into direct contact with persons lights electrical appliances and surfaces before the steam has been totally...

Page 14: ...nection of any simple or automatic humidistat and safety devices such as high limit humidistat air flow proving switch and remote on off The humidi er is operated by the closing of a mechanical humidi...

Page 15: ...tches are used then a jumper must be installed between AB AB DO NOT apply any voltage to AB AB 3 6 3 Connect the ADCD humidistat for Modulating Operation To select signal modulating see Fig 3 y Connec...

Page 16: ...s L1 L 2 GROUND Power supply and Ground connections Power supply 110 VAC 1 phase 50 60Hz 1 86kW or 230VAC 1 phase 50 60Hz 4 05kW KEY Programming port Connecting to Programming port or supervisor GND N...

Page 17: ...eter values 11 ON OFF button 12 Reset button to reset alarms and access parameters 13 Level of output 33 66 100 14 Fan relay is activated 4 3 Starting Elite Steam Insure that the external power is tur...

Page 18: ...aximum Production and exit to the normal operating mode 5 3 Activating Manual Drain Press and hold the drain button on the front of the unit until the cylinder is drained Note Water will continue to f...

Page 19: ...et the alarms although still active alarms will continue to display 5 Using the E2 Humidistat 5 Press toselect OFF MANUALor AUTO mode if outdoor sensor is connected OFF mode The humidifier is turned o...

Page 20: ...r drain is blocked 2 The supply water or over ow circuit has leaks 3 The condensate drain pipe does not bring the water back to the drain pan 4 The steam hose is not properly fastened to the cylinder...

Page 21: ...l before touching it or use protective gloves To replace the cylinder 1 Completely drain the cylinder by pressing and holding the drain button until the cylinder is empty 2 Turn the humidi er off and...

Page 22: ...19 BLOWER FILTER KIT 6 7536 35 20 INTERNAL STEAM DISTRIBUTOR MANIFOLD FOR ROOM VERSION 7 7537 15 3 FILL TEMPERING VALVE ASSEMBLY 110 1 7 7538 35 3 FILL TEMPERING VALVE ASSEMBLY 230 1 8 7539 15 4 DRAI...

Page 23: ...T GRILL FOR RMB 7525 DMNKIT DUCT MOUNT KIT FOR GENERALAIRE DS35 AND DS15 7545 RMB15 REMOTE MOUNT BLOWER KIT 110 1 FOR GENERAL AIRE DS15 7540 RMB35 REMOTE MOUNT BLOWER KIT 230 1 FOR GENERAL AIRE DS35 7...

Page 24: ...ed and operated in accordance with all appropriate manuals and wiring diagrams Replacement of routinely replaceable parts such as steam cylinders and gaskets are not covered by this limited warranty o...

Page 25: ...Elite Steam 03U221903 REV 2 1 25...

Page 26: ...Elite Steam 03U221903 REV 2 1 NOTES 26...

Page 27: ...Elite Steam 03U221903 REV 2 1 27...

Page 28: ...C 43800 GRAND RIVER AVE NOVI MICHIGAN 48375 1115 WWW GENERALAIRE COM CANADIAN GENERAL FILTERS LTD 39 CROCKFORD BLVD SCARBOROUGH ONTARIO M1R3B7 WWW CGFPRODUCTS COM Agency Form 35 5 Rev 2 0 Elite Steam...

Reviews: