3
www.generalfilters.com
Model 570 Humidifier Installation Manual
Unit Location
• WARNING
: Disconnect electrical power before beginning installation.
• Do not install where temperatures fall below 32°F / 0° C or where plenum temperatures exceed 200° F / 93° C.
For maximum evaporative capacity, install this humidifier on the warm air supply plenum.
Additional Materials That May Be Necessary:
1. 1/4" Diameter plastic supply tubing for cold water applications, or 1/4" copper supply tubing for hot water
applications
2. 6" Diameter galvanized by-pass pipe
3. Electrical wire and wire nuts
4. Current sensing relay (Model #GA50 - GFI #7026)
5. #8 Self-piercing sheet metal screws
Specifications
•
Model:
570
DMM or 570DMD
Elite Flow Through Humidifiers (GFI #5710 & #5705)
•
Type:
Flow Through
•
GPD:
12 Based on 120° F / 49° C Plenum Temperature
•
Warranty (Years):
10
•
Replacement Vapor Pad®:
GA10 (GFI#7900) (Replace 1-2 times per season)
•
Dimensions (Inches):
11-7/8 W x 13-3/8 H x 9-1/2 D
•
Weight (Pounds):
7
•
Home Size (Square Feet):
To 2,000
•
Installation:
Warm Air / Return Air Plenum / Right or Left Side
•
Plenum Opening (Inches):
8-7/8 W x 9-1/2 H
•
Bypass Opening (Inches):
6
•
Pallet Qty:
36
•
Cabinet Construction:
UV-Stable Automotive Grade Plastic
•
Humidistat
(Included)
:
“M” Models: MHX3C / “A” Models: GFX3
•
Voltage:
24VAC
•
In The Box:
Humidifier, Humidistat, Control Bypass Damper, 24V Transformer, Solenoid Valve, Vapor Pad
®
,
Saddle Valve, (GCV3412 Code Valve - A Models), Installation Instructions, Template, Parts.
!
11-7/8” W
13-3/8” H
9-1/2” D
Expected Humidity Performance Coverage in Square Feet Based on Construction Type
Model No.
GPD
Loose
(0.75 AC/H)
Average
(0.50 AC/H)
Tight
(0.30 AC/H)
Elite 570
12
800 Sq. Ft.
1200 Sq. Ft.
2000 Sq. Ft.
Elite 900
17
1115 Sq. Ft.
1650 Sq. Ft.
2800 Sq. Ft.
Elite 1000
18
1175 Sq. Ft.
1770 Sq. Ft.
3000 Sq. Ft.
Outside Design Temperature
0° F / -18° C
Outside Design R.H.
70% R.H.
Inside Design Temperature
70° F / 21° C
Inside Design R.H.
30% R.H.
Air Changes/hour (AC/H)
0.30
Ceiling Height (Feet)
8
Furnace Plenum Temperature
120° F / 49° C
Furnace Run Time For Calculating Sq. Ft.
8 Hour /1 Day
Humidifier Performance Baseline Criteria
Installation Options:
•
Warm Air Plenum
•
Return Air Plenum
•
Right or Left Bypass
•
Vertical or Horizontal
•
Furnace or Air Handler