GM9907-L5
bulk scale controller user’s manual
- 49 -
controller will Clear the above Alarm and return the stop state, or enter e-stop to return
the stop state.
View the time, Target, and actual weight of each scale in history. Click
【
Data Edit
】
to
export history data through the U disk or clear historical data .
Note
:Set Delivery ACUM quantity and completed in&outACUM power-off save
4.7
Motor Para.
Motor
Para.
Para.
Description
Filling
para.
1.
Feed Gate
Drive Mode
Initial value
:
Air Drived.
Air Drived
:
air drive control feed gate ON/OFF
;
Motor Drived
:
General motor control feeding door ON and
OFF (1 limit bit: OFF threshold bit
)
The following parameters are the feeding parameters of " Motor Drived "
mode
2.
Filling
Motor Cfg
ID
Feed Motor Para. Group ID
0-4
; Initial value
:
0
,
range
:
0~4
3.
Co-Fill
Gate Open
Time(Co-F)
Feed gate open to coarse feed time
Initial value
:
0.80
,
range
:
0.00~99.99
(
Unit
:
s
)
4.
Fi-Fill Gate
Open Time
(Fi-F)
Feed gate open to fine feed time
Initial value
:
0.20
,
range
:
0.00~99.99
(
Unit
:
s
)
5.
Filler Gate
Close Over
Time
When performing the feeding door closing action, if the
feeding door closing signal is not detected within the time,
the feeding motor will be stopped and Alarm will be
generated
Note: No timeout judgment is performed when the value is
set to 0.
Initial value
:
4.0
,
range
:
0.0~99.9
(
Unit
:
s
)
6.
Filler Gate
Pos. Signal
Initial value
:
ON:If Closed.
ON:If Closed: when the signal is effective, the filler gate
Closed Firmly;
OFF: If closed: when the signal isinvalid, the filler gate
Closed Firmly.