Installation, Tests, & Troubleshooting

12

Owner’s/Installation Manual for SMM

Troubleshooting

See 

Table 3-2

 for troubleshooting problems, causes, and corrections.

Table 3-2. Troubleshooting

Problem

Cause

Correction

Load not powered; LED is OFF

Circuit breaker disabled.

Enable circuit breaker.

Load not powered; LED is OFF

Utility main line circuit breaker (MLCB) 
disabled and generator OFF.

Enable utility MLCB if utility is present or verify 
generator operation if outage.

Load not powered; LED flashing 
1 second interval
 

Generator power just applied to unit.
Utility power just applied to unit.
Generator was overloaded and shed 
occurred.

Wait five minutes plus the priority time delay (see 

Table 2-1

) for unit to enable output.

Load not powered; LED flashing 
3 second interval

This load overloaded the generator while 
attempting recovery from a shed. It is in 
a 30 minute lockout wait period.

Wait 30 minutes from lockout for unit to attempt to re-
apply load.
Review all loads enabled in household. Generator 
may end up in another overload condition when this 
load is enabled. Disable some loads to prevent 
generator overload from recurring.

Load not powered; LED flashing 
6 second interval

The lockout switch is enabled and the 
unit is on generator power.

During installation, it was determined that this load 
will be disabled during generator operation to prevent 
generator overload. Contact IASD for details.

Load not powered while on 
utility

Wiring or unstable frequency.

Check wiring. See 

Setting Lockout 

 for information 

on unstable frequency.

Summary of Contents for G007000-0

Page 1: ...RAC COM 1 888 GENERAC 1 888 436 3722 Para espa ol visita http www generac com service support product support lookup Pour le fran ais visiter http www generac com service support product support looku...

Page 2: ...ii Owner s Installation Manual for SMM 000393a WARNING CANCER AND REPRODUCTIVE HARM www P65Warnings ca gov...

Page 3: ...ation Considerations 3 Smart Management Module SMM 3 SMM and Carton Contents 4 Setting Lockout 5 Jumper Locations 5 Section 3 Installation Tests Troubleshooting Electrical Specifications 9 Enclosure S...

Page 4: ...Table of Contents iv Owner s Installation Manual for SMM This page intentionally left blank...

Page 5: ...es The manufacturer cannot anticipate every possible cir cumstance that might involve a hazard The alerts in this manual and on tags and decals affixed to the unit are not all inclusive If using a pro...

Page 6: ...Introduction and Safety 2 Owner s Installation Manual for SMM This page intentionally left blank...

Page 7: ...e SACM as the top priorities then use additional SMMs as the remaining priorities To reduce the loads returned to the generator all at once it is best to set the SMM priorities to follow after the las...

Page 8: ...sitions are LOCKOUT LOAD ON GENER ATOR enabled and LOCKOUT DISABLED See Table 2 2 NOTE Recovery time is based on priority dial settings See Table 2 1 Test Button C Disables contactor output for a spec...

Page 9: ...ped with two movable jumpers 2 Jumper locations are indicated on the diagram 3 Frequency Jumper default for 60 Hz 4 Mode Selector Jumper identified on control board as Lock Out Jumper position A is de...

Page 10: ...erator mode or during a first time utility power up for five minutes of initial operation Lockout 30 minutes 3 second flash 3 On 3 Off Generator Module detected an overload while trying to recover fro...

Page 11: ...the l oad Module now in lockout recovery NO YES Have load shed recovery time a nd module priority time elapsed 1 YES NO Was lockout recovery operation successful YES NO YES NO Notes 1 Refer to the Pr...

Page 12: ...General Information and Setup 8 Owner s Installation Manual for SMM This page intentionally left blank...

Page 13: ...ditional information Mounting Instructions Recommended installation is near the electrical panel or appliance load The enclosure has a NEMA 3R rating and can be mounted indoors or outdoors It provides...

Page 14: ...rce and load lines to transfer switch and SMM NOTE Suitable conduit fittings must be installed in knockout openings when running supply and load wires Height in mm H1 6 17 156 8 H2 2 36 60 Width in mm...

Page 15: ...ntil power returns during an outage Delay time for post load shed recovery An example configuration is shown below Configurations will vary depending on customer prioritization of loads 1 Set the prio...

Page 16: ...time delay see Table 2 1 for unit to enable output Load not powered LED flashing 3 second interval This load overloaded the generator while attempting recovery from a shed It is in a 30 minute lockou...

Page 17: ...Installation Tests Troubleshooting Owner s Installation Manual for SMM 13 This page intentionally left blank...

Page 18: ...Installation Tests Troubleshooting 14 Owner s Installation Manual for SMM This page intentionally left blank...

Page 19: ......

Page 20: ...rights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W2929...

Reviews: