CRT O - Critical Condition Operations
The Critical Condition Operations menu varies based upon the system's current condition. Any one of three
conditions may exist.
An active critical condition exist: This state is entered when the number of critical input channels that are
simultaneously in the active alarm state meets or exceeds the critical condition threshold.
An inactive critical condition exists: This state is entered from the active critical condition state after the
number of critical input channels that are currently in the active alarm state does not meet or exceed the critical
condition threshold.
No critical condition exists: This state is entered only after a user manually resets the critical condition logic
using the CRT O command.
COMMAND> CRT O
CRITICAL CONDITION OPERATIONS
======== ========= ==========
No critical condition exists.
There are
n
critical input channels currently in the
active alarm
state which does not meet or exceed the critical
condition threshold
of
n
channels.
COMMAND> CRT O
CRITICAL CONDITION OPERATIONS
======== ========= ==========
An inactive critical condition exists.
Resetting the critical condition logic will terminate
all active
critical condition actions.
Do you wish reset the critical condition logic?
(y/n)>Yes
OK.
COMMAND> CRT O
CRITICAL CONDITION OPERATIONS
======== ========= ==========
An active critical condition exists.
There are n critical input channels currently in the active alarm
state, meeting or exceeding the critical condition threshold of n
channels. The critical condition logic cannot be reset until the
number of critical input channels in the active alarm state is
reduced or the critical condition threshold is raised.