This bulletin should be used by experienced personnel as a guide to the installation of the Series 26M Control. Selection 
or  installation  of  equipment  should  always  be  accompanied  by  competent  technical  assistance.  We  encourage  you  to 
contact Gems Sensors or a representative if further information is required. 

Installation 

1.  Install  octal  socket  in  appropriate  enclosure 

using two #6 or #8 screws. 

2.  Install  rail  mount  socket  on  appropriate  rail  

(DIN  mount)  in  appropriate  enclosure  if  appli-
cable. 

3.  Wire  control  per  wiring  diagram  following 

N.E.C and local codes. 

4.  Install control module in socket.  

Warrick

®

 Series 26M Control

 

Installation and Operation Bulletin 

Specifications  

Control  Design:  Solid-state  components  enclosed  in  a  clear  Lexan 
plug-in style housing. Not NEMA rated. 

Contact Design: 1 SPDT (1 form C), powered contacts  
(input Power L1 connected to common of relay contacts)  

Contact  Ratings:  10A@120/240-VAC  resistive  (120°F),  1A 
@120/240VAC resistive (150°F), 1/3 HP @ 120/240-VAC (120°F).  
Contact Life: Mechanical -5 million operations  
Electrical -100,000 operations minimum at rated load  

Supply Voltage: Factory Configured: 24V, 120V, 220V, or 240V AC 
+10%/-15%  of  nominal,  50/60  Hz.  Factory  Configured:  208V/240V 
Model: 187V Min to 242V Max, VAC 50/60 Hz  

Power  Consumption:  24/120/220/240-VAC  with  both  relays  ener-
gized 

~

 4.4 VA.  

Secondary  Circuit:  2.3  VAC  RMS  voltage  on  probes,  <  1  milliam-
pere source capability.  

Sensitivity:  Factory  programmed  to  4.7K,  10K,  26K,  50K,  or  100K 
Ohms 
Operating Ambient Temperature Range: -40°F to +150°F  (-40°C to 
+65°C)  

Terminals: All connections made with screw-clamp terminals.  
Time Delays: Standard LLCO, 0.5 sec. on rising level, 3 sec. on fall-
ing  level.  Optional  0-90  sec.  time  delays  in  1-sec.  increments  for 
rising and falling.  
Listings: Control carries U.L. Limit Control Listing (UL-353) for 
24VAC and 120VAC Line Powered units only (220VAC, 240VAC, 
208/240VAC units not rated

).

 

 

SENSITIVITY  

CHARACTER 

 

SENSITIVITY  

(K-OHMS) 

 

Distance 

(FT) 

 

4.7 

900 

10 

600 

26 

250 

50 

100 

100 

50 

 

∗ 

Based on type MTW or THHN wire,  

       #14 or #16 AWG  

Sensitivity vs. Maximum  

Probe Wire Distance*  

Dimensional Drawing  

Torque all terminals and socket mounting screws to 7 in-lb max. 

Mount the octal socket 
(base) on rigid vertical 

or horizontal surface 
using #6 or #8 screws. 
The control should be 

mounted within an 
enclosure of proper 
NEMA integrity. 