RemoDAQ-8031A/33A/34 User’s Manual
3.11 $AA40
±
VVV.VV
Name
:
Zero adjust
Description
:
Set the zero adjust values for the module
Syntax
:
$AA40
±
VVV.VV(cr)
$ is a delimiter character.
AA address of reading module(00~FF)
4 the zero adjust command.
±
VVV.VV zero adjust value
(cr) is the terminating character, carriage return (0Dh)
Response
:
!AA(cr) if the command was valid.
?AA(cr) if an invalid operation was entered.
Syntax error or communication error may get no response.
! command is valid.
? command is invalid.
AA address of the module (00~FF)
Example
:
Command
:
$0140-000.18 Receive
:
!011
Span address 01 channel zero adjust value –000.18, return
success.
Notice
:
Command only for
RemoDAQ-8031A