RemoDAQ-8054 User’s Manual
RemoDAQ converter module, a personal computer with RS-
232 port (baudrate set to 9600) and theRemoDAQ utility software.
Configuration with the RemoDAQ Utility Software
The easiest way to configure the RemoDAQ module is by
using the RemoDAQ utility software
:
an easy-to-use menu-
structured program will guide you through every step of the
configuration.
Configuration with the
RemoDAQ command set
RemoDAQ modules can also be configured by issuing
direct commands from within a terminal emulation program
that is part of the RemoDAQ utility software.
The following example guides you through the setup of an
analog input module. Assume that RemoDAQ-8054 still has
its default settings (baud rate 9600 and address 01h). Before
the module is reconfigured, it is first requested to send its
default settings.
To change the configuration setting of the analog input
module, the following command is issued
:
%0107400600(cr)
% = change configuration
01 = target module at address 00 to
:
07 = change address to 07 hexadecimal
40 = set input range to Type 40
06 = set baud rate to 9600
00 = set integration time to 50 ms (60 Hz)
disable checksum
set data format to engineering units