TECHNICAL SPECIFICATION

Dimensions

: 72x72mm

Panel Cut-out

: 68x68mm

Display

: 2x4 Digits 7 Segment

Inputs

: START / RESET / GATE

  3 x max. 32VDC (OFF:0..2VDC, ON:7..24VDC)

GATE Input

: Inhibits count-down/up when GATE is ON

Output

: Out1, Out2; 2 x Relay (NO-O-NC), 250VAC, 2A, Resistive load

  SS Out1&Out2; 2xopen collector (NPN), 30V,100mA max.

Time Base

 

: Selectable; 99:59 hours / 99:59 minutes / 599.9 seconds

Resolution

: 1 min. / 1 sec./ 0.1 sec.

Accuracy

: ± 0,5 % (Over full scale)

Modes

: Selectable 8 different modes

Sensor Supply Out

: 12VDC, 50mA max. (unregulated)

Supply Voltage

: 100..240VAC, 50-60Hz or 24Vac/dc (optional)

Power Consumption : < 6VA

Humidity

: 80% up to 30

o

C, then linearly decreases to 50% at 50

o

C (non-condensing)

Altitude

: < 2000 m

EMC

: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)

Safety

: EN 61010-1; Pollution degree 1, measurement category 

I

, (Only light industrial

  environment, double/reinforced isolated, non-conductive pollution environment)

Protection Class

: IP20; according to EN 60529

Storage Temperature : -10

o

C .. 60

o

C (no icing)

Operation Temp.

: 0 .. 50 

o

C

Weight

: < 0.5 kg

Key

: Micro switch

Torque for screwing : Max. 0.5 N.m

no: 

normally open

nc: 

normally closed

Gürbüzo

ğ

lu Elektronik San. ve Tic. Ltd. 

Ş

ti.

http://www.gemo.com.tr

Çamlıtepe Cad. No:297 / 3-4 Siteler, Ankara, Türkiye

e-posta: [email protected]

Tel: +90-312-3503900, Fax: +90-312-3511117

1

14

14

+12V 50mA

+12V 50mA

15

15

START

START

16

16

RESET

RESET

17

17

GATE

GATE

SS Out 1

SS Out 1

SS Out 2

SS Out 2

18

18

19

19

20

20

Gnd

Gnd

+

+

+

+

-

Out

Out

Out

PNP Proximity

Switch

PNP Proximity

Switch

PNP Proximity

Switch

GATE
Switch

RESET
Switch

START
Switch

14

+12V 50mA

15

START

16

RESET

17

GATE

SS Out 1

SS Out 2

18

19

20

Gnd

+

-

30Vdc

(Max)

(*) SS Out
return should
directly
connected to
GND pin.

(**) Use free-
wheeling diode
to protect SS Out.

(*)

(**)