![GEM 567 servoDrive Operating Instructions Manual Download Page 33](http://html1.mh-extra.com/html/gem/567-servodrive/567-servodrive_operating-instructions-manual_2206259033.webp)
www.gemu-group.com
33 / 45
GEMÜ 567 servoDrive
15 Inspection/maintenance
NOTICE
Exceptional maintenance work!
▶
Damage to the GEMÜ product.
●
Any maintenance work and repairs not described in these
operating instructions must not be performed without
consulting the manufacturer first.
The operator must carry out regular visual examination of the
GEMÜ products depending on the operating conditions and
the potential danger in order to prevent leakage and damage.
The product also must be disassembled and checked for
wear in the corresponding intervals.
1. Have servicing and maintenance work performed by
trained personnel.
2. Wear appropriate protective gear as specified in plant op-
erator's guidelines.
3. Shut off plant or plant component.
4. Secure plant or plant component against recommission-
ing.
5. Depressurize the plant or plant component.
6. Actuate GEMÜ products which are always in the same po-
sition four times a year.
15.1 Replacing the actuator
15.1.1 Remove the actuator from the distance piece.
CAUTION
Danger - high voltage!
▶
Electric shock.
●
Before performing any work on the
GEMÜ product switch off power and
protect circuit from being switched on
again.
WARNING
The equipment is subject to pressure!
▶
Risk of severe injury or death.
●
Depressurize the plant.
●
Completely drain the plant.
CAUTION
Hot plant components!
▶
Risk of burns.
●
Only work on plant that has cooled
down.
WARNING
Corrosive chemicals!
▶
Risk of caustic burns.
●
Wear suitable protective gear.
●
Completely drain the plant.
CAUTION
Use of incorrect spare parts!
▶
Damage to the GEMÜ product.
▶
Manufacturer liability and guarantee will be void.
●
Use only genuine parts from GEMÜ.
NOTICE
Important:
▶
After disassembly, clean all parts of contamination. Take
care not to damage the parts in the process. Afterwards,
check parts for potential damage. If parts are damaged,
replace them.
CAUTION
Valve is no longer functioning correctly
▶
Damaged parts are reused.
●
Remove and clean all parts, check for damage and re-
place if necessary.
NOTICE
▶
The piping need not be drained when replacing the actu-
ator, as the valve spindle is sealed by the plug diaphragm.
A
18
17
16
16
18
17
11
1. Move the actuator
A
to the open position.
2. Undo the cap nuts
18
from the stud bolts
16
.
3. Remove the washers
17
.
4. Remove the actuator
A
from the distance piece
11
.
15 Inspection/maintenance